Daewoo RN-331NPW Manuale Utente

Pagina di 38
2. FUNCTIONS
- R HTR 
- COMP 
A. Condition of LOW RT 
  - RT sensor below 19
 
  - When the RT sensor is over 20
, the system comes to be “General Operation Mode”. 
  - When the RT sensor is between 19
°
C to 20
°
C, the system keeps the previous mode. 
B. Control 
  - When the temp of RT sensor is between 14
°
C to 19
°
C, COMP on/off temp is 3
°
C UP  
  - When the temp of RT sensor is below 14
°
C, COMP ON/OFF temp is 4
°
C UP 
 
CONTROL OBJECT 
INPUT 
 
RT 
 
2-4. Function of Low Ambient Temperature (RT) 
 
COMP 
It takes several minutes to protect Compressor: 
   (1) 6 minutes after Comp off 
   (2) 30 minutes at operation of Low RT, but  6 minutes when the doors open more than 20 seconds 
 
CONTROL OBJECT 
INPUT 
 
 2-5. Prevention of Compressor Restart
 
Buzzer 
 
A. When Forced Defrost Mode start, the buzzer rings  3times. 
B. After 2 minutes power’s on, the buzzer rings 3 times. 
C. At Short Circuit Test, the buzzer rings 1 times. 
D. When door opens, the buzzer rings every 1 minute for 5 minutes. 
 
CONTROL OBJECT 
INPUT 
 - Forced Defrost Mode start 
 - Door Switch 
 - Initial Power Input 
 
2-6. Buzzer Sound 
 