Eaton MSD200CM60I Dépliant

Pagina di 2
Eaton Low Voltage Surge Protection - Australia & new Zealand 
1300 3 EATON (1300 3 332 866)       
www.eaton.com/powerquality     www.eatonelectric.com.au
Eaton® MSDI
 
Specifications
Technical Specifications
MSD200CM60i
Input voltage
200 - 250VAC (380 - 440VAC 3 Phase) 
Maximum continuous voltage (MCOV)
320VAC
Temporary overvoltage - TOV
350VAC, 15 mins
Service type
TT, TN, TN C-S or any 3-phase system with a grounded neutral
Energy Absorption rating - per mode (Joules)
Primary Protection L-N = 3,000J/ph, 9,000J total 
Common mode protection L-E = 710J/ph, 2,130J total 
Common mode protection N-E = 2,130J total 
Aggregate rating 13,260J
Recommended max. overcurrent protection
125A GL HRC fuse
Protection modes
Line-Neutral, Line-Earth, Neutral-Earth
In 8/20us (Line-Neutral) Nom. surge life
75kA per phase x 20 times
In 8/20us (Line-Earth) Nom. surge life
15kA per phase x 20 times
In 8/20us (Neutral-Earth) Nom. surge life
45kA x 20 times
Ismax 8/20us (Line-Neutral) Max. surge life
200kA
Ismax 8/20us (Line-Earth) Max. surge life
40kA
Ismax 8/20us (Neutral-Earth) Max. surge life
120kA
Initial clamp voltage (Line-Neutral)
560V (350Vac RMS)
Initial clamp voltage (Line-Earth)
680V (420Vac RMS)
Initial clamp voltage (Neutral-Earth)
680V (420Vac RMS)
Internal protection (fusing)
All surge diverter connections are fused via HRC fuses to IEC269-2-1
Alarms/indicators
Bargraph display for protection remaining, dry contact alarm relay output – 250Vac/32Vdc, 10A, 4kV 
isolation, Alarm under-voltage cutoff 180Vac.
Enclosure rating
IP24
Design Standards:
IEC61643-1, IEC610006-1,2,3,4 ANSI/IEEE C62.41 Cat B,C,D,E AS1768-2007 Cat B,C,D,E AS3000, 
AS3100, CE mark  
Dimensions & Weight
370 x 160 x 560 mm (W x D x H), 14kg
Environment
-10 to 65°C, 10 to 90%RH (non-condensing)
LC
2/23/2005
550192
MS Di S eries
2/23/2005
INP UT
E
E AR TH S TUD
ON C AS E
8mm
MAIN
E AR THING
P OINT (S W B )
MS Di S urge Diverter
C onnection Diagram
T his document is to be us ed in conjunction with
MS Di S urge Diverter Ins tallation G uide
(Tvs s Doc#510065)
NE UTR AL LINK
OR
M.E .N.
L1
L2
L3
MAIN S W B
FUS E
< 3m line distance
Min distance
to floor 600mm
Min distance
to ceiling 300mm
TO LOADS
I
MP OR T ANT
N
OT E S
:
1.
All phase and neutral connections via 8mm bolts .
2.
E arth connection via M8 stud, lower right of enclos ure.
3.
R efer to labelling for connection points .
4.
Always run a separate earth cable, even if the unit is bolted to
the S W B tray.
5.
Keep input and output cables physically separated at all times.
Min. separation distance 500mm.
6.
HR C fuses are preferred to MC B s for connection to main S W B.
S ee P age 2 on installation guide for details .
7.
Unit is to be located within 3m (cable length) of the main system
E arth and Neutral link for point-of-entry application. G reater
lengths reduce protection.
8.1.
E arth wiring: F or proper operation of this MS D it is essential that
a robust and physically short earth connection be made to the
site earthing point. W ith reference to local wiring standards,
earth cables are usually sized against a thermal rating,
determined by expected fault currents, (5,000 to 25,000 amps).
W hen installing an MS D however, the installer must be aware
that surge currents can exceed 50,000 amps, and therefore
heavier cables are generally required to limit voltage drops
under surge conditions. T o achieve these requirements, the
earth cable size should be selected to be equal to, or greater
than, the largest incoming cable into the MS D. T his ensures that
voltage drops on the earth cable are minimis ed.
8.2
Other wiring: All power-carrying conductors shall be sized
according to locally-applicable standards. It is recommended
that the incoming neutral conductor be sized the same as (or
larger than) the phase conducts as it is the primary return for
line-neutral surges.
L3
L2
L1
N
C
M
Y
CM
MY
CY
CMY
K
550192_msdi_cnx_dia_a4.pdf   6/10/2008   1:30:27 PM
Important: Before installing the device, 
please read & follow the installation & 
operation instructions.
1
2
4
3
A
B
C
D
4
3
2
1
D
C
B
A
Title
n
o
i
s
i
v
e
R
r
e
b
m
u
N
Size
A4
 f
o
  
  
t
e
e
h
S
 
6
0
0
2
-
g
u
A
-
7
:
e
t
a
D
File:
C:\tvss engineering\Product_engineering\current\MSF\MSF.ddb
Drawn By:
LINE
NEUTRAL
EARTH STUD
Differential protection.
One phase shown, all phases identical
NO
COM
NC
FROM OTHER PHASES
MSD LINE DIAGRAM
0
1 1
JDP
FPRI
L-N protection
N-E protection
L-E protection
Protection alarm
Common-mode protection.
One phase shown, all phases
 identical
550250
C
M
Y
CM
MY
CY
CMY
K
MSDi_550250.pdf   6/10/2008   1:33:06 PM
Connection & Line Diagram
Due to continual product improvement specifications are subject to change without notice. Copyright 2010 Eaton Corporation.