Eaton MSD200CM60I Dépliant
Eaton Low Voltage Surge Protection - Australia & new Zealand
1300 3 EATON (1300 3 332 866)
www.eaton.com/powerquality www.eatonelectric.com.au
Eaton® MSDI
Specifications
Technical Specifications
MSD200CM60i
Input voltage
200 - 250VAC (380 - 440VAC 3 Phase)
Maximum continuous voltage (MCOV)
320VAC
Temporary overvoltage - TOV
350VAC, 15 mins
Service type
TT, TN, TN C-S or any 3-phase system with a grounded neutral
Energy Absorption rating - per mode (Joules)
Primary Protection L-N = 3,000J/ph, 9,000J total
Common mode protection L-E = 710J/ph, 2,130J total
Common mode protection N-E = 2,130J total
Aggregate rating 13,260J
Recommended max. overcurrent protection
125A GL HRC fuse
Protection modes
Line-Neutral, Line-Earth, Neutral-Earth
In 8/20us (Line-Neutral) Nom. surge life
75kA per phase x 20 times
In 8/20us (Line-Earth) Nom. surge life
15kA per phase x 20 times
In 8/20us (Neutral-Earth) Nom. surge life
45kA x 20 times
Ismax 8/20us (Line-Neutral) Max. surge life
200kA
Ismax 8/20us (Line-Earth) Max. surge life
40kA
Ismax 8/20us (Neutral-Earth) Max. surge life
120kA
Initial clamp voltage (Line-Neutral)
560V (350Vac RMS)
Initial clamp voltage (Line-Earth)
680V (420Vac RMS)
Initial clamp voltage (Neutral-Earth)
680V (420Vac RMS)
Internal protection (fusing)
All surge diverter connections are fused via HRC fuses to IEC269-2-1
Alarms/indicators
Bargraph display for protection remaining, dry contact alarm relay output – 250Vac/32Vdc, 10A, 4kV
isolation, Alarm under-voltage cutoff 180Vac.
Enclosure rating
IP24
Design Standards:
IEC61643-1, IEC610006-1,2,3,4 ANSI/IEEE C62.41 Cat B,C,D,E AS1768-2007 Cat B,C,D,E AS3000,
AS3100, CE mark
Dimensions & Weight
370 x 160 x 560 mm (W x D x H), 14kg
Environment
-10 to 65°C, 10 to 90%RH (non-condensing)
LC
2/23/2005
550192
MS Di S eries
2/23/2005
INP UT
E
E AR TH S TUD
ON C AS E
8mm
MAIN
E AR THING
P OINT (S W B )
MS Di S urge Diverter
C onnection Diagram
T his document is to be us ed in conjunction with
MS Di S urge Diverter Ins tallation G uide
(Tvs s Doc#510065)
NE UTR AL LINK
OR
M.E .N.
L1
L2
L3
MAIN S W B
FUS E
< 3m line distance
Min distance
to floor 600mm
Min distance
to ceiling 300mm
TO LOADS
I
MP OR T ANT
N
OT E S
:
1.
All phase and neutral connections via 8mm bolts .
2.
E arth connection via M8 stud, lower right of enclos ure.
3.
R efer to labelling for connection points .
4.
Always run a separate earth cable, even if the unit is bolted to
the S W B tray.
the S W B tray.
5.
Keep input and output cables physically separated at all times.
Min. separation distance 500mm.
6.
HR C fuses are preferred to MC B s for connection to main S W B.
S ee P age 2 on installation guide for details .
7.
Unit is to be located within 3m (cable length) of the main system
E arth and Neutral link for point-of-entry application. G reater
lengths reduce protection.
lengths reduce protection.
8.1.
E arth wiring: F or proper operation of this MS D it is essential that
a robust and physically short earth connection be made to the
site earthing point. W ith reference to local wiring standards,
site earthing point. W ith reference to local wiring standards,
earth cables are usually sized against a thermal rating,
determined by expected fault currents, (5,000 to 25,000 amps).
W hen installing an MS D however, the installer must be aware
W hen installing an MS D however, the installer must be aware
that surge currents can exceed 50,000 amps, and therefore
heavier cables are generally required to limit voltage drops
under surge conditions. T o achieve these requirements, the
under surge conditions. T o achieve these requirements, the
earth cable size should be selected to be equal to, or greater
than, the largest incoming cable into the MS D. T his ensures that
voltage drops on the earth cable are minimis ed.
voltage drops on the earth cable are minimis ed.
8.2
Other wiring: All power-carrying conductors shall be sized
according to locally-applicable standards. It is recommended
that the incoming neutral conductor be sized the same as (or
that the incoming neutral conductor be sized the same as (or
larger than) the phase conducts as it is the primary return for
line-neutral surges.
L3
L2
L1
N
C
M
Y
CM
MY
CY
CMY
K
550192_msdi_cnx_dia_a4.pdf 6/10/2008 1:30:27 PM
Important: Before installing the device,
please read & follow the installation &
operation instructions.
1
2
4
3
A
B
C
D
4
3
2
1
D
C
B
A
Title
n
o
i
s
i
v
e
R
r
e
b
m
u
N
Size
A4
f
o
t
e
e
h
S
6
0
0
2
-
g
u
A
-
7
:
e
t
a
D
File:
C:\tvss engineering\Product_engineering\current\MSF\MSF.ddb
Drawn By:
LINE
NEUTRAL
EARTH STUD
Differential protection.
One phase shown, all phases identical
NO
COM
NC
FROM OTHER PHASES
MSD LINE DIAGRAM
0
1 1
JDP
FPRI
L-N protection
N-E protection
L-E protection
Protection alarm
Common-mode protection.
One phase shown, all phases
identical
550250
C
M
Y
CM
MY
CY
CMY
K
MSDi_550250.pdf 6/10/2008 1:33:06 PM
Connection & Line Diagram
Due to continual product improvement specifications are subject to change without notice. Copyright 2010 Eaton Corporation.