Technical Data
Features
All rights preserved. Subject to error and change without notice
Product Type
Uninterrupted power supply
line interactive
line interactive
Capacity
1400 VA / 840 W
INPUT
Voltage 230VAC
Voltage Range
162-290VAC
Output
Voltage 230VAC
Voltage Regulation (Battery Mode)
± 10 %
Frequency
50 or 60 Hz
Frequency Regulation (Battery Mode)
± 1 Hz
Output Wave Form
Modified sine wave
Battery
Type and Number
12V battery (9 Ah) x 2
Back-up Time 100W (PC+15" CRT)
45 minutes (around)
Recharge Time
10 hours to 90% after complete discharge
Transfer Time (typical)
4 to 8 ms
Indicator
AC Mode
The 1st green LED lights up ; the LED 2 to 5 light up one by one
indicating the load level
indicating the load level
Back-up Mode
The 1st green LED lights up ; the LED 2 to 5 light up one by one
indicating the load level
indicating the load level
Fault
Red LED is on
Audible Alarm
Back-up Mode
1 sound signal every 10 seconds
Battery Low
1 sound signal every second
Overload
1 sound signal every half-second
Battery exchange
1 sound signal every 2 seconds
Fault
Continuous sound signal
Protection
Full Protection against discharge, overcharge and overload
Environment
Operating Temperature
0 °C - 40 °C
Humidity Relative,
Relative, 0% ~ 90% (non condensing)
Noise Level AC mode:
< 45 dB
Interface
Smart RS-232 Port
No
USB Port
Windows 98/2000/ME/XP/Vista
Dimensions (L x W x H)
368 x 140 x 180 mm
Weight 14.2
kg
Accessory
Software, user guide, cables
Microprocessor control guarantees high reliability
Equipped with Boost and Buck AVR to stabilize input voltage
Built-in DC start function enables UPS to be started up without
AC power supplied
Smart RS-232 Communication Port with Free Download
Software from the Internet
Software from the Internet
User-Replaceable Battery Design
Auto charge even though UPS is off
Auto restart while AC recovery
Provides Modem/Phoneline surge protection
Provides Discharge, Overcharge, Short-Circuit and Overload Protection
USB Port available for optional