The primary display shows ---- until you press the 
T
 button and a valid resistance reading is 
obtained. 
• 
The high voltage symbol (
Y
) along with a primary 
display of >2 V warns if voltage greater than 2 V 
ac or dc is present. In this condition, the test is 
inhibited. Disconnect the Tester and remove 
power before proceeding. 
• 
If the Tester chirps when you press the 
T
 
button, the test is inhibited because voltage is 
present at the probes. 
5.
 
Push and hold the 
T
 button to start the test. The 
t
 icon appears on the lower portion of the display 
until you release the 
T
 button. The resistance 
reading appears on the primary display until a new 
test is started or a different function or range is 
selected. 
When resistance is higher than the maximum display 
range, the Tester displays the > symbol and the 
maximum resistance for the range. 
INSULATION  TESTER
1507
 
bbw04f.eps 
Figure 6. Measuring Earth-Bond Resistance