Curve 3:
With increasing depth
ρ
E is not decreasing: a strip conductor electrode is
advisable.
As measuring results are often distorted and corrupted, for example, by
underground pieces of metal and underground aquifers, a second
measurement, in which the spike axis is turned by an angle of 90 °, is
always advisable (see graph below).
underground pieces of metal and underground aquifers, a second
measurement, in which the spike axis is turned by an angle of 90 °, is
always advisable (see graph below).
H
S
E
ES
90°
I
edw022.eps
Measurement of Resistances
Resistance Measurement (R~)
This measuring function determines the ohmic resistance between 0.02
Ω
and 300 k
Ω
.
The measurement is done with ac voltage. For measurements of very low resistances a
compensation of the connecting leads is suggested (see Compensation of Measuring
Lead Resistance).
compensation of the connecting leads is suggested (see Compensation of Measuring
Lead Resistance).
edw023.eps
Figure 12. Resistance Measurement (R~)
1. Turn central rotary switch to position "R~".
2. Connect instrument as shown in Figure 12.