Testboy TV 455VDE-tester Testboy TV 455 Manuale Utente

Codici prodotto
Testboy TV 455
Pagina di 76
TESTBOY TV 450 
Settings 
 
25 
 
4.2.5 RCD standard 
 
 
In this menu the used standard for RCD 
tests can be set. 
 
Figure 4.6: Selection of RCD test 
standard 
Keys: 
 
UP / DOWN 
Selects standard. 
TEST 
Confirms selected standard. 
Function selectors 
Exits back to main function menu. 
Maximum RCD disconnection times differ in various standards.  
The trip-out times defined in individual standards are listed below.  
 
Trip-out times according to EN 61008 / EN 61009: 
 
½
×I
ΔN
*)
 
I
ΔN
 
2
×I
ΔN
 
5
×I
ΔN
 
General RCDs  
(non-delayed)   t
Δ 
> 300 ms 
t
Δ 
< 300 ms 
t
Δ
 < 150 ms 
t
Δ
 < 40 ms 
Selective RCDs  
(time-delayed)   t
Δ 
> 500 ms  130 ms < t
Δ 
< 500 ms 60 ms < t
Δ
 < 200 ms  50 ms < t
Δ
 < 150 ms
 
Trip-out times according to EN 60364-4-41: 
 
½
×I
ΔN
*)
 
I
ΔN
 
2
×I
ΔN
 
5
×I
ΔN
 
General RCDs 
(non-delayed)   t
Δ 
> 999 ms 
t
Δ 
< 999 ms 
t
Δ
 < 150 ms 
t
Δ
 < 40 ms 
Selective RCDs 
(time-delayed)   t
Δ 
> 999 ms  130 ms < t
Δ 
< 999 ms 60 ms < t
Δ
 < 200 ms  50 ms < t
Δ
 < 150 ms
 
Trip-out times according to BS 7671: 
 
½
×I
ΔN
*)
 
I
ΔN
 
2
×I
ΔN
 
5
×I
ΔN
 
General RCDs 
(non-delayed)   t
Δ 
> 1999 ms 
t
Δ 
< 300 ms 
t
Δ
 < 150 ms 
t
Δ
 < 40 ms 
Selective RCDs 
(time-delayed)   t
Δ 
> 1999 ms  130 ms < t
Δ 
< 500 ms 60 ms < t
Δ
 < 200 ms  50 ms < t
Δ
 < 150 ms
 
Trip-out times according to AS/NZ
**)
 
 
½
×I
ΔN
*)
 
I
ΔN
 
2
×I
ΔN
 
5
×I
ΔN
 
 
RCD type  I
ΔN
 [mA] 
t
Δ
 
t
Δ
 
t
Δ
 
t
Δ
 
Note 
≤ 10 
40 ms 
40 ms 
40 ms 
II 
> 10 
≤ 30 
300 ms  150 ms
40 ms 
III > 
30 
> 999 ms 
300 ms  150 ms
40 ms 
500 ms  200 ms 150 ms
Maximum break time 
IV 
 
S  
 
> 30 
> 999 ms 
130 ms  60 ms 
50 ms 
Minimum non-actuating time 
*) 
Minimum test period for current of ½
×I
ΔN
, RCD shall not trip-out. 
**) 