Testing RCD 
 
36 
5.4 Testing RCDs 
 
Various test and measurements are required for verification of RCD(s) in RCD protected 
installations. Measurements are based on the EN 61557-6 standard. 
The following measurements and tests (sub-functions) can be performed: 
‰
 
Contact voltage, 
‰
 
Trip-out time, 
‰
 
Trip-out current, 
‰
 
RCD autotest. 
 
 
See chapter 4.1 Function selection for instructions on 
key functionality. 
Figure 5.16: RCD test 
 
Test parameters for RCD test and measurement 
 
TEST RCD 
sub-function test [RCDt, RCD I, AUTO, Uc]. 
I
ΔN
 
Rated RCD residual current sensitivity I
ΔN
[10 mA, 30 mA, 100 mA, 300 mA, 
500 mA, 1000 mA]. 
type 
RCD type [ ,  ],  test current waveform plus  starting polarity  [
,
,
,
*, 
*]
MUL 
Multiplication factor for test current  [½, 1, 2, 5 I
ΔN
]. 
Ulim Conventional 
touch voltage limit [25 V, 50 V]. 
* Model TESTBOY TV 450 (TYPE B) 
 
Notes:  
‰
 
Ulim can be selected in the Uc sub-function only. 
 
The instrument is intended for testing of General (non-delayed) and 
S
elective (time-
delayed) RCDs, which are suited for: 
 
‰
 
Alternating residual current (AC type, marked with 
 symbol), 
‰
 
Pulsating residual current (A type, marked with   symbol). 
‰
 
Pulsating residual current (A type, marked with   symbol). 
‰
 
Model TESTBOY TV 450 (Type B): DC residual current (B type, marked with   
symbol). 
 
Time delayed RCDs have delayed response characteristics. As the contact voltage pre-
test or other RCD tests influence the time delayed RCD it takes a certain period to 
recover into normal state. Therefore a time delay of 30 s is inserted before performing 
trip-out test by default.