Example 
INSYS GSM 4.2 LOGO! 
56  
Dezember 
06
 
 
A PT100 temperature sensor is 
connected directly at analog input AI3 
(AM2 PT100 expansion module). 
Limit values are calculated according to 
the following formula: 
Limit = (Temperature/°C x 4) + 200 
 
For an upper limit of +55°C, an upper 
limit of 420 is calculated.  
 
Monitoring only takes place when an 
upper limit is exceeded, so a lower limit 
of 0 is suitable (corresponds to –50°C). 
 
A look at the relevant section of the 
control program reveals that linking 
inputs to circuit elements is not strictly 
necessary to monitor inputs alone. It is only necessary to connect AI3 to a memory 
bit since utilized inputs are not permitted to be open-circuit inputs.  
Using this simple approach, LOGO! can be used solely to expand the inputs of the 
INSYS GSM 4.2 LOGO! 
 
6.5 
Scan of Actual Values 
Scan of fault counter via SMS: 
The following SMS should be sent to the INSYS GSM 4.2 LOGO!: 
BLOCK021? 
 
Scan of exhaust and intake elapsed time counters via SMS: 
The following SMS should be sent to the INSYS GSM 4.2 LOGO!: 
BLOCK016,017?