Initial Operation 
 
INSYS GSM 4.2  
INSYS GSM 4.2 compact 
 
22
 
 
 
 
 
 
 
 
 
 
 
 
Sep-06
 
The serial interface (RS232) of the INSYS GSM and the configuration PC are connected for 
initial operation and configuration.  
For data communication during operation, connect the terminal device with the applica-
tion (e.g. a PLC) via the serial interface with the INSYS GSM (dashed line).  
3.3 
Implementation Overview 
The following steps are required for the implementation: 
1. 
Switch the device on and test it. 
2. 
Initial configuration using HSComm or AT commands. 
3. 
Insert the SIM card. 
4. 
Restart 
3.4 
Switch the Device on and Test it 
1. 
Connect the INSYS GSM and the PC using the serial cable. 
2. 
Connect the GSM antenna. 
3. 
Connect the power supply at the terminals 10..60 VDC and GND.  
 
Caution - Damage of components! 
The given values are maximum values. 
4. 
Switch the power supply on.  
The LED Power will light up. 
The INSYS GSM starts the initialization. 
1. 
LED Connect or LED DCD light up for approx. 4 seconds. 
2. 
After 8 more seconds the LED Status starts to flash for approx. 20 seconds. 
3. 
Afterwards, the LED Status goes out because no SIM card is inserted and no PIN 
is stored.  
4. 
The LED Signal is on or blinks depending on the strength of the GSM network. 
The device is operational. 
If the INSYS GSM does not perform an initialization or the LED Power is not on, refer to 