Inputs & Outputs commands
 
O4:xxxxx 
defines time period for relay 4 action (in seconds) 0 = infinite 
O5:xxxxx 
defines time period for relay 5 action (in seconds) 0 = infinite 
A1:xxxxx 
defines delay for relay 1 reply (in seconds) 0 = no message 
A2:xxxxx 
defines delay for relay 2 reply (in seconds) 0 = no message 
A3:xxxxx 
defines delay for relay 3 reply (in seconds) 0 = no message 
A4:xxxxx 
defines delay for relay 4 reply (in seconds) 0 = no message 
A5:xxxxx 
defines delay for relay 5 reply (in seconds) 0 = no message 
I1:xxx 
debounce time for input 1 (in seconds) 
I2:xxx 
debounce time for input 2 (in seconds) 
I3:xxx 
debounce time for input 3 (in seconds) 
I4:xxx 
debounce time for input 4 (in seconds) 
I5:xxx 
debounce time for input 5 (in seconds) 
V1:x 
1 - invert input 1 
  
0 - normal input 1 
V2:x 
1 - invert input 2 
  
0 - normal input 2 
V3:x 
1 - invert input 3 
   
0 - normal input 3 
V4:x 
1 - invert input 4 
  
0 - normal input 4 
V5:x 
1 - invert input 5 
  
0 - normal input 5 
A1L: 
set analog input 4 low threshold (millivolts) 
A1H: 
set analog input 4 high threshold (millivolts) 
A2L: 
set analog input 5 low threshold (millivolts) 
A2H: 
set analog input 5 high threshold (millivolts) 
BAT: 
set low battery threshold (millivolts) 
BCT: 
set  charger  timeout  -  time  in  seconds  before  device  goes  to  sleep  when  Vcc  is 
disconnected. default is 120; 0 = infinite 
 
Table 3: Inputs & Outputs commands