Bussmann Micro fuse 14 mm x 51 mm 32 A 690 Vac Very quick acting -FF- FWP-32A14FI Content 1 pc(s) FWP-32A14FI Scheda Tecnica

Codici prodotto
FWP-32A14FI
Pagina di 5
For product data sheets, visit www.cooperbussmann.com/DatasheetsEle
234
High Speed Fuses
Ferrule — FWP 690V/700V (IEC/UL): 1-50A,
Striker Optional
Dimensions - mm (in)
51 (2.00")
59 (2.323")
13 (0.511")
14.3
(0.563")
5 (0.197")
FWP (14 x 51mm)
Specifications
Description:
Ferrule style high
speed fuses with and without 
indicating striker.
Dimensions:
See dimensions
illustrations.
Ratings:
Volts: — 690Vac (IEC)
— 700Vac (UL)
— 800Vdc (5-50A)
Amps: — 1-50A
IR: — 200kA RMS Sym.
— 50kA @800Vdc
Agency Information:
CE, UL Recognition JFHR2.E91958,
CSA Component Acceptance file Class 1422-30, 1422-90
(53787) for versions without indicator only. Designed and 
tested to IEC 60269: Part 4.
Electrical 
Characteristics
Total Clearing I
2
t
The total clearing I
2
t at
rated voltage and at power
factor of 15% are given in
the electrical 
characteristics. For other
voltages, the clearing I
2
t is
found by multiplying by
correction factor, K, given
as a function of applied working
voltage, Eg, (rms).
Arc Voltage
This curve gives the peak
arc voltage, UL, which
may appear across the
fuse during its operation
as a function of theapplied
working voltage, Eg, (rms)
at a power factor of 15%.
Power Losses
Watts loss at rated current
is given in the electrical
characteristics. The curve
allows the calculation of
the power losses at load
currents lower than the
rated current. The 
correction factor, Kp, is
given as a function of the
RMS load current, Ib, in %
of the rated current.
Catalog Numbers
Rated
I
2
t (A
2
Sec)
Catalog
Current
Minimum
Clearing At
Watts
Numbers
Size
RMS-Amps
Melting
Rated Voltage
Loss
Without Striker
FWP-1A14F
1
—        
FWP-2A14F
2
FWP-2.5A14F
2.5
FWP-3A14F
3
FWP-4A14F
4
FWP-5A14F
14 x 51mm
5
1.6
11.0
1.5
FWP-10A14F
(
9
16
" x 2")
10
3.6
38.5
4
FWP-15A14F
15
8.6
70
5.5
FWP-20A14F
20
26.0
230
6
FWP-25A14F
25
46.5
375
7
FWP-30A14F
30
58
485
9
FWP-32A14F
32
68
600
7.6
FWP-40A14F
40
84
750
8
FWP-50A14F
50
200
1800
9
With Striker*
FWP-10A14FI
10
3.6
38.5
4
FWP-15A14FI
15
8.6
70
5.5
FWP-20A14FI 14 x 51mm
20
26.0
230
6
FWP-25A14FI
(
9
16
” x 2”)
25
46.5
375
7
FWP-30A14FI
30
58
485
9
FWP-32A14FI
32
68
600
7.6
FWP-40A14FI
40
84
750
8
FWP-50A14FI
50
200
1800
9
*Striker range is 600Vdc only
• Watts loss provided at rated current.
• See accessories on page 243.
Features and Benefits
• Excellent cycling capability and DC performance
• Low arc voltage and low energy let-through (
I2
t)
• Low watts loss in a compact size
• Used with finger-safe holders/blocks
U
L
1.4
1.2
10
3
6
8
7
9
5
4
3
200 300
400
500 600
700
E
g
K
p
1.0
0.8
0.4
0.5
0.6
0.3
0.2
0.1
30 40 50 60 70 80 90 100%
I
b
K
1.4
1.2
1.0
0.6
0.8
0.7
0.9
0.5
0.4
0.3
200 300
400
500 600 700
E
g
1)
2)
1) 5-30A Range
2) 32-50A Range
50.8
(2.000")
15.5
(0.610")
14.3
(0.563")
With Striker
Without Striker
FWP with
striker option.
Electrical Characteristics
Data Sheet: 720025