Bender VMD4105-D-2 B93010045 Scheda Tecnica
Codici prodotto
B93010045
Function
16
3.2.5
Malfunction and messages
In the case of an internal malfunction or an error in the operation of the cou-
pling switches, both alarm LEDs will flash. The error code or the message in
plain text is indicated on the display.
If several faults or messages occur simultaneously, they will be displayed alter-
nately at four-second-intervals.
In the case of an internal error, make a note of the error code "xx" and contact
the Bender Service.
pling switches, both alarm LEDs will flash. The error code or the message in
plain text is indicated on the display.
If several faults or messages occur simultaneously, they will be displayed alter-
nately at four-second-intervals.
In the case of an internal error, make a note of the error code "xx" and contact
the Bender Service.
In case of malfunctions or messages, the power
generation system will be separated from the supply
network.
generation system will be separated from the supply
network.
Code/
Message
Message
LED
Meaning
Remedy
1…20
Both LEDs
flash
flash
Internal error
Make a note from the error
code "xx“ and contact the
Bender Service.
code "xx“ and contact the
Bender Service.
contact
monit. K1
monit. K1
Both LEDs
flash
flash
Error:
Contact
monitoring
K1
Contact
monitoring
K1
After rectifying the the fault
at the coupling switch/main
switch (e.g. manual connec-
tion of the backup switch),
the fault is automatically
cleared. Should, however, a
fault have occurred three
times within 30 seconds, nor-
mal operation must be
started again after fault recti-
fication by pressing the
"RESET" button (in the stand-
ard display).
at the coupling switch/main
switch (e.g. manual connec-
tion of the backup switch),
the fault is automatically
cleared. Should, however, a
fault have occurred three
times within 30 seconds, nor-
mal operation must be
started again after fault recti-
fication by pressing the
"RESET" button (in the stand-
ard display).
contact
monit. K2
monit. K2
Error:
Contact
monitoring
K2
Contact
monitoring
K2