W60AB measuring current transformer
Measuring current transformers of the
W…AB series
W…AB series
Product description
Measuring current transformers of the W…-AB series are measuring current transformers
which in combination with devices of the RCMA420 resp. RCMS460/423 490 series convert
AC and DC currents into evaluable measurement signals. Connection to the respective devices
is via a five-wire or six-wire cable. The CTs can be used in DC, AC, and 3(N) AC systems. If the
measuring current transformers are to be connected to an RCMS460/490 system, one AN420
or AN110 power supply unit is required for six measuring current transformers each.
which in combination with devices of the RCMA420 resp. RCMS460/423 490 series convert
AC and DC currents into evaluable measurement signals. Connection to the respective devices
is via a five-wire or six-wire cable. The CTs can be used in DC, AC, and 3(N) AC systems. If the
measuring current transformers are to be connected to an RCMS460/490 system, one AN420
or AN110 power supply unit is required for six measuring current transformers each.
The measuring current transformers of the W35ABP and W60ABP series feature an integra-
ted Mumetal shield.
ted Mumetal shield.
Standards
The measuring current transformers of the W…-AB series comply with the requirements
of IEC 60044-1.
of IEC 60044-1.
Installation instructions
• Make sure that all live conductors are routed through the measuring current transformer
• Do not route shielded conductors through the measuring current transformer
• Never route a PE conductor through the measuring current transformer!
Device features
• W20AB…W60AB for AC/DC sensitive
RCMA420 series residual current monitors
• W20AB…W210AB for RCMS460 / 490 series
residual current monitoring systems or for
RCMA423 residual current monitors
RCMA423 residual current monitors
• W35ABP…W60ABP for RCMS460 / 490 and
RCMA420 / 423 series residual current
monitors. Suitable for systems where short-
term system-related load currents occur
monitors. Suitable for systems where short-
term system-related load currents occur
Approvalsand certifications