Features
ATEX certified
Rated output voltage: 24 V electronically stabilised/limited
Rated output current In = 125 mA, electronically limited
Wide input voltage range: 18
– 36 V
Easy installation in distribution board on DIN-rails
Applications
SECU-BAR 125 is installed outside of the Ex-zone and provides an intrinsi-
SECU-BAR 125 is installed outside of the Ex-zone and provides an intrinsi-
cally safe output voltage with i
gnition prevention level “ia” and an output
current with ignition prevention level “ib” for electrical equipment in-
stalled in hazardous, flammable environments like
stalled in hazardous, flammable environments like
Industrial sensors for:
Pressure, temperature, humidity, proximity, length, weight
Limit switch position, transducers for non-electrical parameters ...
Electrical equipment in the chemical, petro-chemical industry, tank
farms:
Level indication, overfill prevention, pressure, temperature
Fuelling stations:
Level control systems, overfill prevention systems
Principle of operation
The input voltage is passed via a fuse to a DC-DC-voltage converter which
stabilises the output voltage. Via two electronic current limiting devices in
series the voltage is fed to the output of the barrier. Additional protective
devices provide a power supply for probes in Ex-zone 0. The output voltage
is limited under all circumstances to maximal 25.2 V and the output current
to 131 mA max.
The input voltage is passed via a fuse to a DC-DC-voltage converter which
stabilises the output voltage. Via two electronic current limiting devices in
series the voltage is fed to the output of the barrier. Additional protective
devices provide a power supply for probes in Ex-zone 0. The output voltage
is limited under all circumstances to maximal 25.2 V and the output current
to 131 mA max.
Checking the contents of delivery
Please, check the contents of delivery immediately after receipt and un-
packing. In case of missing components or transport damages contact your
local dealer or a SECU-TECH representative.
Please keep the original packing material if you have to send the instrument
to a service facility. For damages resulting from improper packing the man-
ufacturer cannot overtake any liability.
Keep these operating instructions in case you hand over the instruments to
other persons or if operating personnel has to be trained.
SECU-BAR 125
packing. In case of missing components or transport damages contact your
local dealer or a SECU-TECH representative.
Please keep the original packing material if you have to send the instrument
to a service facility. For damages resulting from improper packing the man-
ufacturer cannot overtake any liability.
Keep these operating instructions in case you hand over the instruments to
other persons or if operating personnel has to be trained.
SECU-BAR 125
Order. No.: HF059
Scope of delivery
SECU-BAR 125
Operating instructions