Alarm Energized/Deenergized: Alarm (EVT) output Energized/Deenergized can be selected. 
 
Alarm Energized
Alarm Deenergized 
Red (EVT) LED
Lights 
Lights 
EVT output 
ON 
OFF 
Alarm HOLD function: Once the alarm is activated, alarm output is held until the power is 
turned off. 
 • 
Loop break alarm output 
[Loop break alarm, Alarm and Heater burnout alarm (option) utilize common output terminals.] 
Detects heater burnout, sensor burnout and actuator trouble. 
Setting range: Loop break alarm action time setting: 0 to 200 minutes 
 
Loop break alarm action span setting   
 
Thermocouple, RTD input : 0 to 150 ( ) or 0.0 to 150.0 ( ) 
 
DC voltage, current input  : 0 to 1500 
 
(The placement of the decimal point follows the selection) 
Output: Open collector, Control capacity, 24V DC    0.1A (Max.) 
Converter function: See “7. Converter function” 
Insulation • Dielectric strength: Circuit insulation configuration 
 
 
 
 
 
 
 
 
 
 
 
          Insulation resistance: 10M   or more, at 500V DC   
          Dielectric strength : 1.5kV AC for 1 minute between input terminal and power terminal 
1.5kV AC for 1 minute between output terminal and power terminal 
Power consumption   : Approx. 6VA   
Ambient temperature : 0 to 50  
Ambient humidity      : 35 to 85%RH (no condensation) 
Weight   
: Approx.120g 
External dimensions : 22.5 x 75 x 100mm (W x H x D) 
Material       
: Flame-resistant resin (Case) 
Color     
: Ash gray (Case) 
Attached functions   
[Set value lock] 
[Sensor correction]
   
[Power failure countermeasure] 
The setting data is backed up in non-volatile IC memory. 
[Self diagnosis] 
The CPU is monitored by a watchdog timer, and when an abnormal status is found on the CPU, 
the controller is switched to warm-up status with all outputs turned off. 
[Automatic cold junction temperature compensation] (Only thermocouple input) 
This detects the temperature at the connection terminal between the thermocouple and the 
instrument and always maintains it on the same status as when the reference junction is located   
at 0  (32 ). 
[Warm-up indication] 
After the power supply to the instrument is turned on, the sensor input characters and   
temperature unit are indicated on the PV display and input range high limit value is indicated 
on the SV display for 3 seconds. 
For DC current, voltage input, the scaling high limit value is indicated. 
[Burnout] 
When the thermocouple or RTD input is burnt out, OUT is turned OFF and PV display flashes 
” (for DC current output type, OUT low limit value). 
 
EVT
CT input
Input
CPU
Insulated
Power supply
OUT
5
4
3
9
8
1
2
7
6
Communication
When OUT is non-contact
voltage output or DC current   
output, OUT is not insulated 
from Communication.