Siemens SPS starter kit 6ED1057-3BA10-0AA8 6ED1057-3BA10-0AA8 Scheda Tecnica
Codici prodotto
6ED1057-3BA10-0AA8
User interface
2.8 Menu bar
LOGO!Soft Comfort Online Help
118
Operating Instructions, 06/2014
Function Block
Data type
Read/Write Parameter settings in
LOGO!Soft Comfort
Parameter settings on a partner
device
Aq
VW
R
Kc
VW
R/W
0 to 9999
Integeration Time (TI)
VW
R/W
Unit: Minutes
0 to 5999
Direction
VB
R/W
+
0
-
1
Manual Output (Mq)
VW
R/W
0 to 1000
min
VW
R/W
-10000 to 20000
max
VW
R/W
-10000 to 20000
Gain
VW
R
-1000 to 1000
Offset
VW
R
-10000 to 10000
Analog Filter
Dialog Parameter Averge
Dialog Parameter Averge
Value Sample Number
VB
R/W
3 to 8
8
3
16
4
32
5
64
6
128
7
256
8
Ax
VW
R
Aq
VW
R
Max/Min
Mode
Mode
VB
R/W
0, 1, 2 and other value
Ax
VW
R
Minimum Value
VW
R
Maximum Value
VW
R
Aq
VW
R
When reset=0, reset
Min/Max
VB
R/W
0 or 1
Average Value
Sample Time
Sample Time
VW
R/W
Unit: Seconds or Minutes Value range: 0 to 59
Unit: Hours
Unit: Hours
Value range: 0 to 23
Unit: Days
Value range: 0 to 365
Number of Samples
VW
R/W
Unit: Seconds
Value range: 1 to St*100
Unit: Days
Value range: 1 to 32767
Unit: Hours
Value range: 1 to 32767
Unit: Seconds and ≤ 5
Minutes
Value range: 1 to St*6000
Unit: Seconds and ≥ 6
Minutes
Value range: 1 to 32767
Ax
VW
R