5.3 Special functions 
LOGO!Soft Comfort Online Help 
Operating Instructions, 06/2014 
277
 
●  PI controller: AQ 
●  Up/Down counter: Cnt 
For the 0BA7 and 0BA8 devices, you can additionally use the actual values of the following 
already-programmed functions: 
●  On-delay: Ta 
●  Off-delay: Ta 
●  On-/off-delay: Ta 
●  Retentive on-delay: Ta 
●  Wiping relay(pulse output): Ta 
●  Edge triggered wiping relay: Ta 
●  Asynchronous pulse generator: Ta 
●  Stairway light switch: Ta 
●  Multiple function switch: Ta 
●  Stopwatch: AQ 
●  Analog filter: AQ 
●  Average value: AQ 
●  Max/Min: AQ 
●  Threshold trigger: Fre 
You select the required function by the block number. 
Parameter p (number of decimals) 
Parameter p applies to the display of V1, V2, V3, V4 and AQ in a message text. 
Description of the function 
The mathematic instruction function combines the four operands and three operators to form 
an equation. The operator can be any one of the four standard operators: +, -, *, or /. For 
each operator, you must set a unique priority of High ("H"), Medium ("M"), or Low ("L"). The 
high operation will be performed first, followed by the medium operation, and then by the low 
operation. You must have exactly one operation of each priority. The operand values can 
reference another previously-defined function to provide the value. The mathematic 
instruction function rounds the result to the nearest integer value. 
The number of operand values is fixed at four and the number of operators is fixed at 3. If 
you need to use fewer operands, use constructions such as " + 0" or " * 1" to fill the 
remaining parameters. 
You can also configure the behavior of the function when the Enable parameter "En"=0. The 
function block can either retain its last value or be set to 0.