Reference material 
 
5.3 Special functions 
 
LOGO!Soft Comfort Online Help 
306
 
Operating Instructions, 06/2014 
Timing diagram for AQ 
 
Description of function 
If the input En is set, then the function sets the value StSp + Offset "B" for 100 ms. 
Then, depending on the connection of Sel, the function runs from the level StSp + Offset "B" 
to either level 1 or level 2 at the acceleration set in Rate. 
If the input St is set, the function runs to a level of StSp + B at the acceleration set in Rate. 
Then the function holds the level at StSp + Offset "B" for 100 ms. After 100 ms, the level is 
set to Offset "B". Output AQ. The scaled value (output AQ) is 0. 
If the input St is set, the function can only be restarted once the inputs St and En have been 
reset. 
If input Sel has been changed, depending on the connection of Sel, the function runs from 
the current target level to the new target level at the rate that is specified. 
If the input En is reset, the function immediately sets the current level to Offset "B". 
The current level is updated every 100 ms. Note the relationship between output AQ and the 
current level: 
Output AQ = (current level – Offset "B" ) / Gain "A" 
Particular characteristics to be noted when configuring 
For help on analog block parameters, refer to the Analog value processing (Page 286) 
section. 
 
Special functions (Page 212)