LOGO! functions
4.4 Special functions list - SF
LOGO!
Manual, 06/2014, A5E33039675
Manual, 06/2014, A5E33039675
229
The number of operand values is fixed at four and the number of operators is fixed at 3. If
you need to use fewer operands, use constructions such as + 0 or * 1 to fill the remaining
parameters.
You can also configure the behavior of the function when the Enable parameter En=0. The
You can also configure the behavior of the function when the Enable parameter En=0. The
function block can either retain its last value, or be set to 0. If the parameter Qen → 0 = 0,
then the function sets AQ to 0 when En=0. If the parameter Qen → 0 = 1, then the function
leaves AQ at its last value when En=0.
Possible errors: zero division and overflow
If the mathematic instruction function block execution results in zero division or overflow, it
sets internal bits that indicate the type of error that occurred. You can program a mathematic
instruction error detection function block in your circuit program to detect these errors, and to
control the program behavior as needed. You program one mathematic instruction error
detection function block to reference one specific mathematic instruction function block.
Examples
The following tables show some simple example mathematic instruction block parameters,
and the resulting equations and output values:
V1
Op1
(Priority)
V2
Op2
(Priority)
V3
Op3
(Priority)
V4
12
[+]
6
(/)
3
-
1
Equation: [12 + (6 / 3)] - 1
Result: 13
Result: 13
V1
Op1
(Priority)
V2
Op2
(Priority)
V3
Op3
(Priority)
V4
2
(+)
3
[*]
1
+
4
Equation: 2 + [3 * (1 + 4)]
Result: 17
Result: 17
V1
Op1
(Priority)
V2
Op2
(Priority)
V3
Op3
(Priority)
V4
100
(-)
25
/
2
[+]
1
Equation: (100 - 25) / [2 + 1]
Result: 25
Result: 25