LOGO! functions 
 
4.4 Special functions list - SF 
 
LOGO! 
236
 
Manual, 06/2014, A5E33039675 
Timing diagram (example) 
 
Functional description 
ERst = 1 and En = 0: the function sets the AQ value to 0.  
ERst = 1 and En = 1: the function outputs a value at AQ, depending on the settings of Mode 
and S1.  
ERst = 0 and En = 0: the function holds the value of AQ at the current value.  
ERst = 0 and En = 1: the function outputs a value at AQ, depending on the settings of Mode 
and S1.  
Mode = 0: the function sets AQ to the minimum value 
Mode = 1: the function sets AQ to the maximum value 
Mode = 2 and S1 = 0: the function sets AQ to the minimum value 
Mode = 2 and S1 = 1: the function sets AQ to the maximum value 
Mode = 3: the function outputs current analog input value.  
Setting the Par parameter 
View in programming mode (example) 
 
View in parameter assignment mode (example)