Technical data 
 
A.17 Technical data: LOGO! CSM12/24 
 
LOGO! 
316
 
Manual, 06/2014, A5E33039675 
 
LOGO! CSM12/24 
Delay resulting from latency 
When a frame passed through the CSM12/24, the stored and 
forward function of the switch delays the frame according to the 
characteristics below: 
• 
With a 64 byte frame length by approx. 8 μs (at 100 Mbps). 
• 
With a 1518 byte frame length by approx. 125 μs (at 100 
Mbps). 
Topology 
Star and bus topology 
Note that the direct connection of two ports on the switch or 
accidental connection over several switches causes an illegal loop. 
Such a loop can lead to network overload and network failures. 
Insulation of the ports 
You need shield all ports with each other that adhere to 1.5 kV 
insulation voltage. 
Learnable MAC addresses 
1024 
Aging time 
300 seconds 
Electrical specification 
Input voltage 
(permitted range) 
12 VDC to 24 VDC 
(10.2 VDC to 30.2 VDC) 
Current consumption 
12 VDC: 0.2 A 
24 VDC: 0.1 A 
Effective power loss 
1.5 W 
Connection 
Per terminal for L+ and M 
Cable cross section: 1 x 2.5 mm
or 2 x 1.5 mm
2
 
Tightening torque 0.57 Nm (5 lb in) 
Use 75 °C conductors only. Use copper conductors only. 
Functional grounding 
You can achieve functional grounding by connecting a cable from 
terminal 3, for example to the DIN rail. 
Keep this cable as short as possible. 
Grounding is, however, not necessary for interference-free 
operation. 
Further technical specifications 
Operating temperature 
0 °C to 55 °C 
Transport/storage temperature  -40 °C to +70 °C 
Relative humidity during 
operation 
< 90% (no condensation) 
Dimensions (W x H x D) in mm  72 x 90 x 55 
Net weight 
140 g 
Installation 
35 mm DIN rail (DIN EN 60715 TH35) or wall mounting 
Degree of protection 
IP20 
Protection class 
III