Siemens SPS starter kit 6ED1057-3BA10-0AA8 6ED1057-3BA10-0AA8 Scheda Tecnica
Codici prodotto
6ED1057-3BA10-0AA8
Technical data
A.17 Technical data: LOGO! CSM12/24
LOGO!
316
Manual, 06/2014, A5E33039675
LOGO! CSM12/24
Delay resulting from latency
When a frame passed through the CSM12/24, the stored and
forward function of the switch delays the frame according to the
characteristics below:
•
•
With a 64 byte frame length by approx. 8 μs (at 100 Mbps).
•
With a 1518 byte frame length by approx. 125 μs (at 100
Mbps).
Topology
Star and bus topology
Note that the direct connection of two ports on the switch or
Note that the direct connection of two ports on the switch or
accidental connection over several switches causes an illegal loop.
Such a loop can lead to network overload and network failures.
Such a loop can lead to network overload and network failures.
Insulation of the ports
You need shield all ports with each other that adhere to 1.5 kV
insulation voltage.
Learnable MAC addresses
1024
Aging time
300 seconds
Electrical specification
Input voltage
(permitted range)
Input voltage
(permitted range)
12 VDC to 24 VDC
(10.2 VDC to 30.2 VDC)
(10.2 VDC to 30.2 VDC)
Current consumption
12 VDC: 0.2 A
24 VDC: 0.1 A
24 VDC: 0.1 A
Effective power loss
1.5 W
Connection
Per terminal for L+ and M
Cable cross section: 1 x 2.5 mm
Cable cross section: 1 x 2.5 mm
2
or 2 x 1.5 mm
2
Tightening torque 0.57 Nm (5 lb in)
Use 75 °C conductors only. Use copper conductors only.
Use 75 °C conductors only. Use copper conductors only.
Functional grounding
You can achieve functional grounding by connecting a cable from
terminal 3, for example to the DIN rail.
Keep this cable as short as possible.
Grounding is, however, not necessary for interference-free
Keep this cable as short as possible.
Grounding is, however, not necessary for interference-free
operation.
Further technical specifications
Operating temperature
Operating temperature
0 °C to 55 °C
Transport/storage temperature -40 °C to +70 °C
Relative humidity during
Relative humidity during
operation
< 90% (no condensation)
Dimensions (W x H x D) in mm 72 x 90 x 55
Net weight
Net weight
140 g
Installation
35 mm DIN rail (DIN EN 60715 TH35) or wall mounting
Degree of protection
IP20
Protection class
III