Phoenix Contact I/O module AXL AI 8 2688064 2688064 Scheda Tecnica

Codici prodotto
2688064
Pagina di 10
Nov 13, 2013    2 / 10
Technical data
General
Note on weight specifications
with plugs and bus base module
Mounting type
DIN rail
Protection class
III, IEC 61140, EN 61140, VDE 0140-1
Test section
5 V communications power (logic), 24 V supply (I/O) 500 V AC 50
Hz 1 min
Test section
5 V supply (logic)/functional earth ground 500 V AC 50 Hz 1 min
Test section
24 V supply (I/O) / functional earth ground 500 V AC 50 Hz 1 min
Conformance with EMC directives
Noise immunity test in accordance with EN 61000-6-2 Electrostatic
discharge (ESD) EN 61000‑4‑2/IEC 61000‑4‑2 Criterion B; 6 kV
contact discharge, 8 kV air discharge
Conformance with EMC directives
Noise immunity test in accordance with EN 61000-6-2
Electromagnetic fields EN 61000‑4‑3/IEC 61000‑4‑3 Criterion A;
Field intensity: 10 V/m
Conformance with EMC directives
Noise immunity test in accordance with EN 61000-6-2 Fast
transients (burst) EN 61000‑4‑4/IEC 61000‑4‑4 Criterion B, 2 kV
Conformance with EMC directives
Noise immunity test in accordance with EN 61000-6-2 Transient
surge voltage (surge) EN 61000‑4‑5/IEC 61000‑4‑5 Criterion B;
supply lines DC: ±0.5 kV/±0.5 kV (symmetrical/asymmetrical); ±1
kV to shielded I/O cables
Conformance with EMC directives
Noise immunity test in accordance with EN 61000-6-2 Conducted
interference EN 61000‑4‑6/IEC 61000‑4‑6 Criterion A; Test voltage
10 V
Conformance with EMC directives
Noise emission test according to EN 61000-6-3 Radio interference
properties EN 55022 Class B
Mechanical tests
Vibration resistance in acc. with EN  60068-2-6/IEC  60068-2-6 5 g
Mechanical tests
Shock in acc. with EN  60068-2-27/IEC  60068-2-27 25 g, 11 ms
period, half-sine shock pulse
Mechanical tests
Continuous shock according to EN 60068-2-27/IEC 60068-2-27 10
g
Interfaces
Name
Axioline F local bus
Connection method
Bus base module
Transmission speed
100 MBit/s
Axioline potentials
Communications power U
bus
5 V DC (via bus base module)
Current consumption from U
bus
typ. 105 mA
Current consumption from U
bus
max. 130 mA
Supply of analog modules U
A
24 V DC
Current consumption from U
A
typ. 35 mA
Current consumption from U
A
max. 45 mA
Analog inputs
Number of inputs
max. 8 (Differential inputs, voltage or current can be chosen
separately)
Connection method
Push-in technology
Connection method
2-wire (shielded, twisted pair)