Chapter 3  
3.6  Field Wiring Considerations
•  When you use USB-4716 to acquire data from outside, noises in the 
environment might significantly affect the accuracy of your measure-
ments if due cautions are not taken. The following measures will be 
helpful to reduce possible interference running signal wires between 
signal sources and the USB-4716.
•  The signal cables must be kept away from strong electromagnetic 
sources such as power lines, large electric motors, circuit breakers or 
welding machines, since they may cause strong electromagnetic inter-
ference. Keep the analog signal cables away from any video monitor, 
since it can significantly affect a data acquisition system.
•  If the cable travels through an area with significant electromagnetic 
interference, you should adopt individually shielded, twisted-pair wires 
as the analog input cable. This type of cable has its signal wires twisted 
together and shielded with a metal mesh. The metal mesh should only 
be connected to one point at the signal source ground.
•  Avoid running the signal cables through any conduit that might have 
power lines in it.
•  If you have to place your signal cable parallel to a power line that has a 
high voltage or high current running through it, try to keep a safe dis-
tance between them. Or place the signal cable in a right angle to the 
power line to minimize the undesirable effect.