ADAM-6000 Series User Manual
118
6.3.2 Modbus Function Code Introductions 
To fullfill the programming requirement, there is a series of function code 
standard for users reference¦
Code (Hex)  Name
Usage 
01
Read Coil Status
Read Discrete Output Bit 
02
Read Input Status
Read Discrete Input Bit
03
Read Holding Registers
04       
Read Input Registers 
Read 16-bit register. 
Used to read integer or floating
point process data. 
05
Force Single Coil
Write data to force coil On/Off
06
Preset Single Register
Write data in 16-bit format
08
Loopback Diagnosis
Diagnostic testing of the 
communication port 
15
Force Multiple Coils
Write multiple data to force coil
On/Off
16
Preset Multiple Registers   Write data in 16-bit format
Function Code 01 
The function code 01 is used to read the discrete outputs ON/OFF status 
of ADAM-6000 modules in a binary data format.
Request message format for function code 01:
  
Example: Read coil number 1 to 8 (address number 00017 to 00024) from 
ADAM-6000 Modules
         01 01 00 17 00 08
                                                 Command Body
Station 
Address
Function 
Code
Start 
Address 
High Byte
Start 
Address 
Low Byte
Requested 
Number of Coil 
High Byte
Requested 
Number  of 
Coil Low Byte