ADAM-6000 Series User Manual
144
Example command: $01B07(cr)
response: !0112
Since the ADAM-6018 is used, we can know the range code of
channel 7 is 12, meaning “Thermocouple R (500~1750° C)”.
6.4.4 Analog Input Alarm Command Set Set 
(ADAM-6015, 6017, 6018) 
$aaCjAhs 
Name
Set Alarm Mode
Description Sets the High/Low alarm of the specified input channel in 
the addressed ADAM-6000 module to either Latching or 
Momentary mode.
Syntax          $aaCjAhs(cr) 
$ is a delimiter character.
aa (range 00-FF) represents the 2-character hexadecimal 
slave network address of an ADAM-6000 module. 
(Always 01)
Cj identifies the desired channel j (j : 0 to 7).
Command 
Syntax
Command 
Name
Description 
$aaCjAhs
Set Alarm 
Mode
Set the High/Low alarm in either Momentary or Latch-
ing mode 
$aaCjAh
Read Alarm 
Mode
Returns the alarm mode for the specified channels
$aaCjAhEs
Enable/Dis-
able Alarm
Enables/Disables the high/low alarm of the specified 
channels
$aaCjCh
Clear Latch 
Alarm
Resets a latched alarm
$aaCjAhCCn Set Alarm 
Connection
Connects the High/Low alarm of a specified input 
channel to interlock with a specified output channel
$aaCjRhC           Read  Alarm 
Connection
Returns the alarm configuration of a specified input 
channel 
$aaCjAhU
Set Alarm 
Limit
Sets the High/Low alarm limit value to a specified 
channel 
$aaCjRhU
Read Alarm 
Limit
Returns the High/Low alarm limit value of the speci-
fied channel 
$aaCjS
Read Alarm 
Status
Reads whether an alarm occurred in the specified 
channel