ADAM-6000 Series User Manual
176
The Input Condition stage is a logic condition decision for the input data. 
The decision result will be logic True or False, sending to the Logic stage 
for logic operation. Take analog input mode as example, you can define 
the condition as if the analog input value is greater than a specific value 
(the limit). So when the input value becomes greater than the limit, the 
input stage will transfer True to the Logic stage. Otherwise, it will trans-
fer False to the Logic stage. 
When you click the Input Condition stage icon, you should see a dialog 
window similar to Figure 7.3 below. You can choose the input mode by 
the Mode combo box. The default mode is NoOperation, meaning there 
is no input condition. You can choose local analog input channel (AI)
local digital input channel (DI), local counter input channel 
(DI_Counter), local frequency input channel (DI_Frequency), internal 
timer (Timer), internal flag (AuxFlag) , local digital output channel 
(DO) and internal counter (Counter) as the input mode. After you choose 
the appropriate input mode and complete all related setting, click the OK 
button. That Input Condition stage icon will change its pattern to present 
the current condition. We will describe each mode in more detail below. 
Figure 7.3: Input Condition Stage Configuration
Local Analog Input Channel (AI)
Below are the steps to configure analog input condition: