Figure 7.11: Remote Message Output
Note: The total message sent out will include Device Description, the 
logic rule number which sends this message, the message index, module 
IP, module name and all I/O status.  
 
Local Internal Counter Setting (Counter)
Below are the steps to configure internal counter setting:
1.
Define what action (increase one count to internal counter value by 
Positive edge trigger (F->T), or reset internal counter by Reset
will be taken for the true action (When the logic result value passed 
from Execution stage is logic True) by the True Action combo 
box.
Note: When you choose Positive edge trigger (F->T) as action, the coun-
ter will only add one count for the first time that the logic result value 
from Execution Stage is logic high. After the first time, the counter value 
will not change even the logic result value from Execution Stage is still 
logic high. So it is the reason why it is called positive edge trigger.