210
You can see that DO 0 will only be triggered when rising edge of DI 0 
occurs. In the example project we provide, the DO status will remain 
logic high for 1 second. Then it will back to logic low. When PLC is used 
for this kind of application, the ladder diagram will look similar to Figure 
7.32 below:
Figure 7.32: Ladder Diagram for Rising Edge
When you use GCL to achieve rising edge application, 3 logic rules, 1 
Internal Timer (Timer 0) and 1 Internal Flag (Flag 0) are needed. Refer to 
Figure 7.33 below for GCL logic architecture. With logic rule 3, DO 0 
value is controlled by DI 0 and Flag 0. Flag 0 is initially set as False
When rising edge occurs (DI value changes from logic low to logic high), 
DO will be activated (logic rule 3 are satisfied), and Timer 0 starts to 
count time (logic rule 1 are satisfied). After Timer 0 counts up to the spe-
cific time interval (1 second), Flag 0 will become logic True by logic rule 
2, making DO 0 value logic low (logic rule 3 are not satisfied). The GCL 
architecture is similar to the ladder diagram.
(     )
T0
[        ]
T0 ≧ 1
(     )
DI 0
(     )
Flag0
DO 0
DI 0
Flag0