18
Figure 3.4: Secure Module to a DIN-rail
3.3 Wiring & Connections
This section provides basic information on wiring the power supply, I/O
units, and network connection.
units, and network connection.
3.3.1 Power Supply Wiring
Although the ADAM-6000/TCP systems are designed for a standard
industrial unregulated 24 VDC power supply, they accept any power unit
that supplies within the range of +10 to +30 VDC. The power supply rip-
ple must be limited to 200 mV peak-to-peak, and the immediate ripple
voltage should be maintained between +10 and +30 VDC. Screw termi-
nals +Vs and GND are for power supply wiring.
industrial unregulated 24 VDC power supply, they accept any power unit
that supplies within the range of +10 to +30 VDC. The power supply rip-
ple must be limited to 200 mV peak-to-peak, and the immediate ripple
voltage should be maintained between +10 and +30 VDC. Screw termi-
nals +Vs and GND are for power supply wiring.
Note: The wires used should be at least 2 mm.