26
•  Operating Humidity: 20 ~ 95 % RH (non-condensing)
•  Storage Humidity: 0 ~ 95 % RH (non-condensing)
•  Operating Temperature: -10 ~ 70° C
•  Storage Temperature: -20 ~ 80° C
Application Wiring
Figure 4.2: ADAM-6017 Analog Input Wiring 
ADAM-6017 is built with a 120 resistor in each channel, users do not 
have to add any resistors in addition for current input measurement. Just 
adjust the jumper setting to choose the specific input type you need. Refer 
to Figure 4.3, each analog input channel has built-in a jumper on the PCB 
for users to set as a voltage mode or current mode.