When the communication between host PC and ADAM-6000 digital 
modules is broken, the digital output channel can generate a predefined 
value (this value is called fail safe value). You can enable or disable this 
function by click the Turn on WDT checked channel when WDT trig-
gered
 check box. You can define the fail safe value by the WDT check 
box next to the DO status LED. After configure related setting, click the 
Apply WDT button. Take Figure 5.13 below as example. The fail safe 
value function is enabled. If the communication between ADAM-6000 
digital module and host PC is broken, channels 0 and 2 will automatically 
generate logic high value, while channels 1, 3, 4, 5 will automatically 
generate logic low value.
Figure 5.13: Fail Safe Value Configuration
  
2.
Modbus
You can see current digital input or digital output values for all related 
Modbus address.
Individual Channel Configuration
You can see digital input value and configure setting for each digital input 
channel. It is the same that you can control the digital output value and 
configure setting for each digital output channel. Simply click the channel 
interested in the Individual Channel Configuration items. 
If you choose a digital input channel, the Status Display area should look 
similar to Figure 5.14 below.