Wago 750-553 Fieldbus Independent I/O Module 750-553 Scheda Tecnica
Codici prodotto
750-553
750-553 [4 AO DC 0-20 mA] • 11
Process Image
WAGO-I/O-SYSTEM 750
I/O Modules
I/O Modules
More Information
Detailed references to the approvals are listed in the document "Overview
Approvals WAGO-I/O-SYSTEM 750", which you can find on the CD ROM
ELECTRONICC Tools and Docs (Item-No.: 0888-0412)
or in the internet under:
Detailed references to the approvals are listed in the document "Overview
Approvals WAGO-I/O-SYSTEM 750", which you can find on the CD ROM
ELECTRONICC Tools and Docs (Item-No.: 0888-0412)
or in the internet under:
System Description
2.1.1.6 Process
Image
The analog output module 750-553 transmits 16-bit data and 8 status bits per
channel.
channel.
The digitalized output value is transmitted in a data word (16 bits) as output
byte 0 (low) and output byte 1 (high) via the process image of the coupler /
controller.
This value is represented with a 12 bit resolution on bit B3 ... B14.
The three least significant bits (B0 ... B2) are not parsed.
byte 0 (low) and output byte 1 (high) via the process image of the coupler /
controller.
This value is represented with a 12 bit resolution on bit B3 ... B14.
The three least significant bits (B0 ... B2) are not parsed.
Some fieldbus systems can process the status information using by means of a
status byte.
However, processing of the status byte via the coupler / controller is optional,
which means that accessing or parsing the status information depends on the
fieldbus system.
status byte.
However, processing of the status byte via the coupler / controller is optional,
which means that accessing or parsing the status information depends on the
fieldbus system.
2.1.1.6.1 Standard
Format
For the standard module 750-553, the numerical values ranging from 0x0000
to 0x7FFF are scaled on the output current ranging from 0 mA to 20 mA.
to 0x7FFF are scaled on the output current ranging from 0 mA to 20 mA.
Process values of module 750-553
numerical value
Output-
current
binary
Status-
byte
Error-
LED
0 – 20 mA
output value
hex.
dec.
hex.
0 '0000.0000.0000.0000'
0x0000
0
0x00
off
5 '0001.1111.1111.1111'
0x1FFF
8191
0x00
off
10 '0011.1111.1111.1111'
0x3FFF
16383
0x00
off
15 '0101.1111.1111.1111'
0x5FFF
24575
0x00
off
20 '0111.1111.1111.1111'
0x7FFF
32767
0x00
off
Broken wire
or
inadmissible
load
combination
load
combination
'XXXX.XXXX.XXXX.XXXX' 0xXXXX
X 0x40 on