4.2.1. Error acknowledgment 
Three different options are available for error acknowledgement:
Manual (Reset button): 
• Actuate the Reset button on the device front side.
If the Reset button is actuated again after approx. 2 s, the hybrid motor starter adopts the error status 
again.
If the acknowledgment request (pressed reset button) is pending for more than 6 s, the device switches 
to the "Parameterization" state.
Manual (remote acknowledgement operating point): 
• Connect a button (N/O contact) between the MAN and RES terminals.
An acknowledgement is triggered if a positive edge is identified at the MAN input. If a negative edge is not 
identified after approx. 2 s, the hybrid motor starter adopts the error status again, since the possibility of 
a manipulation or a defect in the acknowledgement circuit cannot be ruled out.
Automatic: 
• Establish an electrical connection between the RES and AUTO terminals.
After the activation of the bimetal monitoring and a subsequent cooling, the device carries out an 
automatic acknowledgement.
The RES terminal provides the voltage for a reset. 
 
In variants with the rated control supply voltage of 24 V DC, this is 24 V DC and in the case of 
230 V AC, it is a special system voltage.
4.2.2. Feedback 
If the hybrid motor starter detects an error, the feedback relay is activated, i.e. the N/O contact is closed 
or the N/C contact is opened. This behavior corresponds to that of a motor protecting switch or a 
motor overload protection relay.
The feedback is used for signaling and is not a part of the safety chain. It is thus not included in the 
safety monitoring.
4.3. Parameterization - Nominal current setting 
• Actuate the Reset button for more than 6 s in 
order to switch to the "Parameterization" 
operating mode; the green LED PWR flashes 
again. 
In the Parameterization mode, the LEDs are 
switched off after every 2 s for 0.3 s in order to 
different this mode from other operating modes.
• Set the nominal current of the drive using the 
240° potentiometer. The nominal current is 
specified in 16 stages. The four LEDs display the 
set current. 
• Save the value by actuating the Reset button 
again (non-volatile range of the data memory). 
• Actuate the Reset button for more than 2 s (and 
less than 6 s) to display the set current for 3 s. 
 
This function is possible only if 
 
1) the device is not activated, and 
 
2) there is no defect in the device.
From a motor current of 45 A, the 
blocking monitoring is activated 
(see 8.1. Trigger characteristic).
Code
Nominal current [mA]
Variant:
PWR ERR ladj. ON
0.6 A
2 A
9 A 
0
0
0
0
75
180
1500
0
0
0
1
110
250
2000
0
0
1
0
145
410
2500
0
0
1
1
180
560
3000
0
1
0
0
215
710
3500
0
1
0
1
250
870
4000
0
1
1
0
285
1020
4500
0
1
1
1
320
1170
5000
1
0
0
0
355
1330
5500
1
0
0
1
390
1480
6000
1
0
1
0
425
1630
6500
1
0
1
1
460
1790
7000
1
1
0
0
495
1940
7500
1
1
0
1
530
2090
8000
1
1
1
0
565
2250
8500
1
1
1
1
600
2400
9000