Tele 2390000 G2PF400VS02 Gamma 3-Phase Voltage Monitoring Relay 3-phase voltage monitoring 2390000 Scheda Tecnica
Codici prodotto
2390000
Subject to alterations and errors
Release 02/04
Monitoring relays - GAMMA series
Voltage monitoring in 3-phase mains
Monitoring of phase sequence and phase failure
Detection of reverse voltage
Connection of neutral wire optional
Supply voltage = measuring voltage
2 change-over contacts
Width 22.5mm
Industrial design
Technical data
1. Functions
Monitoring of phase sequence, phase failure and detection of return
voltage (by means of evaluating the asymmetry)
voltage (by means of evaluating the asymmetry)
2. Time ranges
Adjustment
range
Start-up suppression time:
fi xed, max. 500ms
Tripping delay:
fi xed, max. 350ms
3. Indicators
Green LED ON:
indication of supply voltage
Yellow LED ON/OFF:
indication of relay output
4. Mechanical design
Self-extinguishing plastic housing, IP rating IP40
Mounted on DIN-Rail TS 35 according to EN 50022
Mounting position:
Mounted on DIN-Rail TS 35 according to EN 50022
Mounting position:
any
Shockproof terminal connection according to VBG 4 (PZ1 required),
IP rating IP20
Tightening torque:
IP rating IP20
Tightening torque:
max. 1Nm
Terminal capacity:
1 x 0.5 to 2.5mm² with/without multicore cable end
1 x 4mm² without multicore cable end
2 x 0.5 to 1.5mm² with/without multicore cable end
2 x 2.5mm² fl exible without multicore cable end
5. Input circuit
Supply voltage:
3(N)~ 115/66V
terminals (N)-L1-L2-L3 (G2PF115VS02)
(= measuring voltage)
3(N)~ 230/132V
terminals (N)-L1-L2-L3 (G2PF230VS02)
(= measuring voltage)
3(N)~ 400/230V
terminals (N)-L1-L2-L3 (G2PF400VS02)
(= measuring voltage)
Tolerance:
3(N)~ 115/66V
3(N)~ 99 to 132V
(G2PF115VS02)
3(N)~ 230/132V
3(N)~ 198 to 264V
(G2PF230VS02)
3(N)~ 400/230V
3(N)~ 342 to 457V
(G2PF400VS02)
Rated frequency:
48 to 63Hz
Rated consumption:
3(N)~
3(N)~
115/66V 3VA
(G2PF115VS02)
3(N)~
230/132V 6VA
(G2PF230VS02)
3(N)~
400/230V 9VA
(G2PF400VS02)
Duration of operation:
100%
Reset time:
<100ms
Residual ripple for DC: -
Drop-out voltage:
Drop-out voltage:
>20% of the supply voltage
Overvoltage category:
III (according to IEC 60664-1)
Rated surge voltage:
4kV
6. Output circuit
2 potential free change-over contacts
Rated voltage:
Rated voltage:
250V AC
Switching capacity (distance <5mm):
750VA (3A / 250V AC)
Switching capacity (distance >5mm):
1250VA (5A / 250V AC)
Fusing:
5A fast acting
Mechanical life:
20 x 10
6
operations
Electrical life:
2 x 10
5
operations
at 1000VA resistive load
Switching frequency:
max. 60/min at 100VA resistive load
max. 6/min at 1000VA resistive load
(according to IEC 947-5-1)
Overvoltage category:
III (according to IEC 60664-1)
Rated surge voltage:
4kV
7. Measuring circuit
Measured variable:
AC Sinus, 48 to 63Hz
Input:
3(N)~ 115/66V
terminals (N)-L1-L2-L3 (G2PF115VS02)
(= supply voltage)
3(N)~ 230/132V
terminals (N)-L1-L2-L3 (G2PF230VS02)
(= supply voltage)
3(N)~ 400/230V
terminals (N)-L1-L2-L3 (G2PF400VS02)
(= supply voltage)
Overload capacity:
3(N)~ 115/66V
3(N)~ 132/76V
(G2PF115VS02)
3(N)~ 230/132V
3(N)~ 264/152V
(G2PF230VS02)
3(N)~ 400/230V
3(N)~ 457/264V
(G2PF400VS02)
Input resistance:
3(N)~
3(N)~
115/66V
5k
Ω (G2PF115VS02)
3(N)~
230/132V 10k
Ω (G2PF230VS02)
3(N)~
400/230V 15k
Ω (G2PF400VS02)
Asymmetry:
fi xed, typ. 30%
Overvoltage category:
III (according to IEC 60664-1)
Rated surge voltage:
4kV
8. Accuracy
Base accuracy:
-
Frequency response:
-
Adjustment accuracy:
-
Repetition accuracy:
-
Voltage infl uence:
-
Temperature infl uence:
-
9. Ambient conditions
Ambient temperature:
-25 to +55°C (according to IEC 68-1)
-25 to +40°C (according to UL 508)
Storage temperature:
-25 to +70°C
Transport temperature:
-25 to +70°C
Relative humidity:
15% to 85%
(according to IEC 721-3-3 class 3K3)
Pollution degree:
3 (according to IEC 60664-1)
Vibration resistance:
10 to 55Hz 0.35mm
(according to IEC 68-2-6)
Shock resistance:
15g 11ms (according to IEC 68-2-27)
G2PF...S02
1.01-5