Technical data
Supply voltage A1 / A2:
230V AC
- 15% / + 10%
A3 / A2:
24V AC/DC
+/- 15%
Frequency range:
0 / 50 ... 60Hz
Power consumption:
0,8 W ; approx. 6 VA with 230V AC
Operating mode:
continuous
Supply voltage influence:
< 0.01% over voltage range
Temperature influence:
< 0.01%/°C
Recovery time:
> 100ms
Repetitive accuracy:
0.2%
Timing range :
0,05s - 10min (8 time ranges)
Operation indicators
Supply voltage:
LED, green
Relay in working position:
LED, yellow
Contact
Number of changeovers:
2
Contact material:
AgNi 0,15
Maximum switching voltage:
400V AC
Maximum switching current:
8A
Maximum switching power :
2000VA
Maximum starting current
30 A
contact live :
30 x 10
6
(mechanical)
Drop-off time of switching element:
approx. 20ms
General data
Ambient temperature:
- 25 ... + 60°C
Mounting position:
any
LVD 2006/95/EG :
61812-1
EMC Dir. 2004/108/EG :
61812-1
overvoltage category :
3 (300V)
contamination degree :
2 (250V)
Isolation : 15/16/18 -> A1/A2/A3/B1/B2
basic isolation (250V)
25/26/28 -> A1/A2/A3/B1/B2
basic isolation (250V)
15/16/18 -> 25/26/28
double isolation (250V)
Connection terminals:
Crosshead screws; M3.5 self-opening
Connection cross section:
2 x 2.5mm²
Mounting:
Symmetrical rail DIN EN 50022
Dimensions l x w x h:
90mm x 17.5mm x 69.5mm
Weight:
104g
X
28
25 26
15
A2
16 18
16 18
A3
A1
X
X
ZSD
Mounting
Snap-on mounting using a standard DIN rail EN 50022.
The unit is designed to allow side-by-side mounting, with an ambient temperature of < 60°C.
The unit is designed to allow side-by-side mounting, with an ambient temperature of < 60°C.
Time
0,5-10 min
3
2
1
1,5-30 s
3
2
1
5-100 s
3
2
1
0,15-3 s
3
2
1
15-300 s
3
2
1
0,5-10 s
3
2
1
0,05-1 s
3
2
1
3-60 s
3
2
1