Tele 1340300 E1PF400VSY01 Gamma 3-Phase Voltage Monitoring Relay 3-phase voltage monitoring 1340300 Scheda Tecnica

Codici prodotto
1340300
Pagina di 2
Subject to alterations and errors
Release 09/06
Monitoring relays - ENYA series
Voltage monitoring in 3-phase mains
Monitoring of phase sequence and phase failure
Monitoring of asymmetry
Connection of neutral wire optional
Supply voltage = measuring voltage
1 change over contact
Width 17.5 mm
Installation design
Technical data
1. Functions
Monitoring of phase sequence, phase failure and asymmetry with 
adjustable asymmetrie, connection of neutral wire optional.
2. Time ranges
  
Adjustment 
range
Tripping delay: 
fixed, approx. 100ms
3. Indicators
Green LED ON: 
indication of supply voltage
Yellow LED ON/OFF: 
indication of relay output
4. Mechanical design
Self-extinguishing plastic housing, IP rating IP40
Mounted on DIN-rail TS 35 according to EN 50022
Mounting position:            any
Shockproof terminal connection according to VBG 4 (PZ1 required),
IP rating IP20
Tightening torque:            max. 1Nm
Terminal capacity:
      1 x 0.5 to 2.5mm
with/without multicore cable end
      1 x 4mm
without multicore cable end
      2 x 0.5 to 1.5mm
2
 with/without multicore cable end
      2 x 2.5mm
2
 flexible without multicore cable end
5. Input circuit
Supply voltage: 
(=measured voltage)
Terminals: (N)-L1-L2-L3
Rated voltage Un: 
see table ordering information or
 
printing on the unit
Tolerance: 
-30% to +30% of Un
Rated consumption: 
8VA (0,8W)
Rated frequency: 
AC 48 to 63Hz
Duty cycle: 
100%
Reset time: 
500ms
Hold-up time: 
-
Drop out voltage: 
>20% of the supply voltage
Overvoltage category: 
III (according to IEC 60664-1)
Rated surge voltage: 
4kV
6. Output circuit
1 potential free change over contact
Rated voltage: 
250V AC
Switching capacity: 
1250VA (5A / 250V AC)
Fusing: 
5A fast acting
Mechanical life: 
20 x 10
6
 operations
Electrical life: 
2 x 10
5
 operations
 
at 1000VA resistive load
Switching frequency: 
max. 60/min at 100VA resistive load
 
max. 6/min at 1000VA resistive load
 
(according to IEC 947-5-1)
Overvoltage category: 
III. (according to IEC 60664-1)
Rated surge voltage: 
4kV
7. Measuring circuit
Measuring variable: 
3(N)~, sinus, 48 to 63Hz
Measuring input: 
(=supply voltage)
Terminals: (N)-L1-L2-L3
Overload capacity: 
determined by tolerance 
 specifi ed for supply voltage
Input resistance: 
-
Asymmetry: 
see table ordering information
Overvoltage category: 
III (according to IEC 60664-1)
Rated surge voltage: 
4kV
8. Accuracy
Base accuracy: 
±5%
Adjustment accuracy: 
≤5%
Repetition accuracy: 
±2%
Voltage influence: 
-
Temperature influence: 
≤0.05% / °C
9. Ambient conditions
Ambient temperature: 
-25 to +55°C (according to IEC 68-1)
Storage temperature: 
-25 to +70°C
Transport temperature: 
-25 to +70°C
Relative humidity: 
15% to 85%
 
(according to IEC 721-3-3 class 3K3)
Pollution degree: 
2, if built in 3
 
(according to IEC 664-1)
Vibration resistance: 
10 to 55 Hz 0.35mm
 
(according to IEC 68-2-6)
Shock resistance: 
15g 11ms
 
(according to IEC 68-2-27)
10. Weight
Single packing: 
 
72g
Packing of 10pcs: 
 
670g per Package