Tele 1340201 E1IU5AAC01 Gamma 1-Phase Current Monitoring Relay 1-phase current monitoring in 230 V/AC network 1340201 Scheda Tecnica

Codici prodotto
1340201
Pagina di 2
Subject to alterations and errors
Release 10/06
Monitoring relays - ENYA series
AC current monitoring in 1-phase mains
Undercurrent monitoring
1 change over contact
Width 17.5 mm
Installation design
Technical data
1. Functions
AC current monitoring in 1-phase mains with adjustable threshold and 
fi xed hysteresis.
UNDER  
Undercurrent 
monitoring
2. Time ranges
  
 
Adjustment 
range
Tripping delay (Delay):   
             -
 
3. Indicators
     Green LED ON/OFF:   
indication of supply voltage
     Yellow LED ON/OFF:   
indication of output relay
4. Mechanical design
Self-extinguishing plastic housing, IP rating IP40
Mounted on DIN-rail TS 35 according to EN 50022
Mounting position: 
any
Shockproof terminal connection according to VBG 4 (PZ1 required), 
IP rating IP20
Tightening torque: 
max. 1Nm
Terminal capacity:
 
1 x 0.5 to 2.5mm² with/without multicore cable end
 
1 x 4mm² without multicore cable end
 
2 x 0.5 to 1.5mm² with/without multicore cable end
 
2 x 2.5mm² flexible without multicore cable end
5. Input circuit
Supply voltage: 
230V AC
Terminals: Li-N
Tolerance: 
-15% to +15% of Un
Rated voltage : 
5VA (0.8W)
Rated frequency: 
AC 48 to 63Hz
Duration of operation: 
100%
Reset time: 
500ms
Wave form: 
Sinus
Hold-up time: 
-
Drop-out voltage: 
>20% of rated voltage
Overvoltage category: 
III (according to IEC 60664-1)
Rated surge voltage: 
4kV
6. Output circuit
1 potential free change over contact
Rated voltage: 
250V AC
Switching capacity: 
1250VA (5A / 250V)
Fusing: 
5A fast acting
Mechanical life: 
20 x 10
6
 operations
Electrical life: 
2 x 10
5
 operations
 
at 1000VA resistive load
Switching frequency: 
max. 60/min at 100VA resistive load
 
max. 6/min at 1000VA resistive load
 
(according to IEC 947-5-1)
Overvoltage category: 
III. (according to IEC 60664-1)
Rated surge voltage: 
4kV
7. Measuring circuit
Measuring variable: 
AC sinus, 48 to 63Hz
Measuring input: 
5A AC
Terminals: Li, 
Lk
Overload capacity: 
7A (ex 5A - distance > 5mm)
Starting current:
               1s 
40A
               3s 
20A
Input resistance: 
10mΩ
Switching threshold Is: 
see table ordering information or
 
printing on the unit
Hysteresis H: 
see table ordering information or
 
printing on the unit
Overvoltage category: 
III (according to IEC 60664-1)
Rated surge voltage: 
4kV
8. Accuracy
Base accuracy: 
±5% of nominal value
Adjustment accuracy: 
±5% of nominal value
Repetition accuracy: 
≤2% of nominal value
Voltage influence: 
-
Temperature influence: 
0,05% / °C
9. Ambient conditions
Ambient conditions: 
-25 to +55°C (according to IEC 68-1)
Storage temperatur: 
-25 to +70°C
Transport temperature: 
-25 to +70°C
Relative humidity: 
15% to 85%
 
(according to IEC 721-3-3 class 3K3)
Pollution degree: 
2, if built-in 3
 
(according to IEC 664-1)
Vibration resistance: 
10 to 55 Hz 0.35mm
 
(according to IEC 68-2-6)
Shock resistance: 
15g 11ms
 
(according to IEC 68-2-27)
10. Weight
Single packing: 
 
70g
Package of 10pcs:   
660g per package
E1IU