Phoenix Contact Monitoring relay EMD-FL-3V-690 2885249 2885249 Scheda Tecnica

Codici prodotto
2885249
Pagina di 4
Nov 10, 2013    2 / 4
Technical data
Input data
Function
Undervoltage, window, asymmetry, phase sequence, phase failure
Min. setting range
-30 % ... 20 % (From U
N
)
Max. setting range
-20 % ... 30 % (From U
N
)
Min setting range of the voltage threshold value
483 V AC ... 828 V AC
Max. setting range of the voltage threshold value
552 V AC ... 897 V AC
Setting range for response delay
0.1 s ... 10 s
Basic accuracy
± 5 % (of scale end value)
Setting accuracy
≤ 5 % (of scale end value)
Repeat accuracy
≤ 2 %
Asymmetry
5 % ... 25% / OFF
Recovery time
500 ms
Contact side
Contact type
2 floating PDT contacts
Maximum switching voltage
250 V AC (in acc. with IEC 60664-1)
Interrupting rating (ohmic load) max.
750 VA (3 A/250 V AC, module aligned, ≤ 5 mm spacing)
Interrupting rating (ohmic load) max.
1250 VA (5 A/250 V AC, module not aligned, ≥ 5 mm spacing)
Output fuse
5 A (fast-blow)
Power supply
Supply voltage range
110 V AC ... 500 V AC (see Power modules)
General
Mechanical service life
Approx. 2 x 10
7
 cycles
Operating mode
100% operating factor
Mounting position
Any
Assembly instructions
on standard DIN rail NS 35 in accordance with EN 60715
Electromagnetic compatibility
Conformance with EMC Directive 2004/108/EC
Surge voltage category
III, basic insulation (as per EN 50178)
Housing insulation material
Polyamide PA, self-extinguishing
Color
green
Rated insulation voltage
600 V (According to EN 50178)
Conformance
CE-compliant
UL, USA / Canada
UL/C-UL listed UL 508
Connection data
Conductor cross section stranded min.
0.25 mm²
Conductor cross section stranded max.
2.5 mm²
Conductor cross section solid min.
0.5 mm²
Conductor cross section solid max.
2.5 mm²
Conductor cross section AWG/kcmil min.
20
Conductor cross section AWG/kcmil max
14
Stripping length
8 mm