Overcurrent monitoring (OVER, OVER+Latch)
When the supply voltage U is applied, the output relay R switches into 
on-position, if the measured current is below the Max-value.
When the measured current exceeds the Max-value, the output relay R 
switches into off-position after the interval of the tripping delay (Delay) 
has expired.
OVER:
The output relay R switches into on-position again, if the current falls 
below the Min-value.
OVER+Latch:
The output relay R switches only into on-position again by interrupting 
and re-applying of the supply voltage, provided that the measured cur-
rent is below the Max-value.
Untercurrent monitoring (UNDER, UNDER+Latch)
When the supply voltage U is applied, the output relay R switches into 
on-position, if the measured current is beyond the Min-value.
When the measured current falls below the Min-value, the output 
relay R switches into off-position after the interval of the tripping delay 
(Delay) has expired.
UNDER:
The output relay R switches into on-position again, if the current 
exceeds the Max-value.
UNDER+Latch:
The output relay R switches only into on-position again by interrupting 
and re-applying of the supply voltage, provided that the measured cur-
rent is beyond the Min-value.
Window function (WIN, WIN+Latch)
When the supply voltage U is applied, the output relay R switches into 
on-position, if the measured current is within the adjusted window.
When the measured current leaves the window between Min and 
Max, the output relay R switches into off-position after the interval of 
the tripping delay (Delay) has expired.
WIN:
The output relay R switches into on-position again, if the current re-
enter the adjusted window.
WIN+Latch:
The output relay R switches only into on-position again by interrupting 
and re-applying of the supply voltage, provided that the measured 
current is within the threshold values.
Latch
latch activated
Latch
latch activated
Latch
latch activated
Functions
E1IM