Tele 2390103 G2TF01 Gamma Temperature Monitoring Relay, PTC Temperature monitoring with a PTC 2390103 Scheda Tecnica
Codici prodotto
2390103
Subject to alterations and errors
www.tele-power-net.com
G2TF01
Functions
If the supply voltage U is applied (green LED illuminated) and the
cumulative resistance of the PTC-circuit is less than 3.6k
cumulative resistance of the PTC-circuit is less than 3.6k
Ω (standard
temperature of the motor), the output relay switches into on-position.
Pressing the test/reset key under this conditions forces the output
relay to switch into off-position. They remain in this state as long as
the test/reset key is pressed and thus the switching function can be
checked in case of fault. The test function is not effective using an
external reset key.
When the cumulative resistance of the PTC-circuit exceeds 3.6k
Pressing the test/reset key under this conditions forces the output
relay to switch into off-position. They remain in this state as long as
the test/reset key is pressed and thus the switching function can be
checked in case of fault. The test function is not effective using an
external reset key.
When the cumulative resistance of the PTC-circuit exceeds 3.6k
Ω (at
least one of the PTCs has reached the cut-off temperature), the out-
put relay switches into off-position (red LED illuminated). The output
relay again switch into on-position (red LED not illuminated), if the
cumulative resistance drops below 1.8k
put relay switches into off-position (red LED illuminated). The output
relay again switch into on-position (red LED not illuminated), if the
cumulative resistance drops below 1.8k
Ω by cooling down of the PTC
and either a reset key (internal or external) was pressed or the supply
voltage was disconnected and re-applied.
voltage was disconnected and re-applied.
Connections
Dimensions