Vision Akkus VISION 6FM134DX, 12V Ah lead acid battery 6FM134DX 6FM134DX Scheda Tecnica

Codici prodotto
6FM134DX
Pagina di 2
6FM134D-X
12V 134Ah(20hr)
The rechargeable batteries are lead-lead dioxide systems. The dilute sulfuric acid electrolyte 
is absorbed by separators and plates and thus immobilized. Should the battery be accidentally 
overcharged producing hydrogen and oxygen, special one-way valves allow the gases to 
escape thus avoiding excessive pressure build-up. Otherwise, the battery is completely 
sealed and is, therefore, maintenance-free, leak proof and usable in any position. 
Battery Construction
General Features 
Absorbent Glass Mat (AGM) technology 
for efficient gas recombination of up to 
99% and freedom from electrolyte 
maintenance or water adding.
Not restricted for air transport-complies 
with IATA/ICAO Special Provision A67.
UL-recognized component.
Can be mounted in any orientation.
Computer designed lead, calcium tin alloy 
grid for high power density.
Long service life, float or cyclic 
applications.
Maintenance-free operation.
Low self discharge.
Dimensions and Weight
Length(mm / inch)
341 / 13.4
Width(mm / inch)
173 / 6.81
Height(mm / inch) 
283 / 11.1
Total Height(mm / inch) 
287 / 11.3
Approx. Weight(Kg / lbs) 
40 / 88.2 
Performance Characteristics 
Nominal Voltage
12V
Number of cell
6
Design Life 
10 years 
Nominal Capacity 77
o
F(25
o
C)
20 hour rate (6.7A, 10.5V)
134Ah
10 hour rate (13.1A, 10.5V)
131Ah
5 hour rate (22.1A, 10.5V)
110.5Ah
1 hour rate (83.6A, 9.6V)
83.6Ah
Internal Resistance
Fully Charged battery 77
o
F(25
o
C)
3.8mOhms
Self-Discharge
3% of capacity declined per month at 20
o
C(average)
Operating Temperature Range
Discharge
-20~60
o
C
Charge
-10~60
o
C
Storage
-20~60
o
C
Max. Discharge Current 77
o
F(25
o
C)
950A(5s)
Short Circuit Current
2250A
Charge Methods: Constant Voltage Charge 77
o
F(25
o
C)
        Maximum charging current
40.2A
        Temperature compensation 
-30mV/
o
C
        Temperature compensation 
-20mV/
o
C
Discharge Constant Current (Amperes at 77
o
F25
o
C)
Discharge Constant Power (Watts at 77
o
F25
o
C)
page1 of 2
(Note)The above characteristics data are average values obtained within 
three charge/discharge cycles not the mimimum values.
End Point
Volts/Cell
5min 10min 15min 30min 1h
3h
5h
10h
20h
1.60V
388
294
239
135
83.6 34.3 23.3 13.3 6.80
1.65V
363
278
230
131
83.0 33.5 23.0 13.2 6.78
1.70V
338
263
220
127
81.3 32.8 22.5 13.1 6.75
1.75V
312
247
210
122
78.9 32.1 22.1 13.1 6.70
1.80V
287
232
201
119
76.3 31.2 21.7 13.0 6.67
End Point
Volts/Cell
5min 10min 15min 30min 45min 1h
2h
3h
5h
1.60V
666
531
423
256
181
168
92.6 66.0 45.9
1.65V
632
504
409
248
178
165
91.1 65.2 45.7
1.70V
599
478
396
242
174
163
89.4 64.4 45.3
1.75V
567
453
382
234
169
158
87.8 63.7 45.0
1.80V
531
423
369
226
166
153
86.9 62.5 44.6
7
3
Cycle use                                                     2.30-2.35VPC
Standby use                                                 2.23-2.27VPC
Component
Positive plate
Negative plate
Container
Cover
Safety valve
Terminal
Separator
Electrolyte
Raw material
Lead dioxide
Lead
ABS
ABS
Rubber
Copper
Fiberglass
Sulfuric acid