4.6.2  Safety checks 
Before the initial use, check the effectiveness of the safety measure(s) of the system accord-
ing to the nationally applicable regulations (e.g.:ÖVE/ÖNORM E8001-6-61, DIN VDE 0100-
600:2008-06 "Checks,...")! 
 
Electrical systems or devices must be checked by the installer of the system or device before 
their initial operation. This also applies for the expansion or modification of existing systems 
or electrical devices. 
 
However, it is essential that all conditions for the safety measures are observed. 
 
Moreover, the following points are to be taken into account: 
 
► 
The checks (continuity of the connections of the protective conductor, insulation 
resistance, RCD (FI) triggering current, triggering time,…) are to be performed for the 
expanded or modified part. 
 
► 
The measurement devices must comply with the national regulations! 
(e.g.: DIN EN 60557 (VDE 0413) "Electrical safety in low-voltage distribution systems 
up to AC 1000V and DC 1500V"). 
 
► 
The measurement results are to be documented. A test report is to be created and 
saved before the check.