6.6 High-speed counter (HSC) 
Easy Book 
Manual, 03/2014, A5E02486774-AF 
121
 
Selecting the functionality for the HSC 
All HSCs function the same way for the same counter mode of operation. Counter mode, 
direction control, and initial direction are assigned in the CPU device configuration for HSC 
function properties. 
There are four basic types of HSC:  
●  Single-phase counter with internal direction control 
●  Single-phase counter with external direction control 
●  Two-phase counter with 2 clock inputs 
●  A/B phase quadrature counter 
You can use each HSC type with or without a reset input. When you activate the reset input 
(with some restrictions, see the following table), the current value is cleared and held clear 
until you deactivate the reset input. 
●  Frequency function: Some HSC modes allow the HSC to be configured (Type of 
counting) to report the frequency instead of a current count of pulses. Three different 
frequency measuring periods are available: 0.01, 0.1, or 1.0 seconds. 
The frequency measuring period determines how often the HSC calculates and reports a 
new frequency value. The reported frequency is an average value determined by the total 
number of counts in the last measuring period. If the frequency is rapidly changing, the 
reported value will be an intermediate between the highest and lowest frequency 
occurring during the measuring period. The frequency is always reported in Hertz (pulses 
per second) regardless of the frequency measuring period setting. 
●  Counter modes and inputs: The following table shows the inputs used for the clock, 
direction control, and reset functions associated with the HSC. 
The same input cannot be used for two different functions, but any input not being used 
by the present mode of its HSC can be used for another purpose. For example, if HSC1 
is in a mode that uses two built-in inputs but does not use the third external reset input 
(default assignment at I0.3), then I0.3 can be used for edge interrupts or for HSC 2. 
Table 6- 30  Counting modes for HSC 
Type 
Input 1 
Input 2 
Input 3 
Function 
Single-phase counter with 
internal direction control 
Clock 
Count or frequency 
Reset 
Count 
Single-phase counter with 
external direction control 
Clock 
Direction 
Count or frequency 
Reset 
Count 
Two-phase counter with 2 
clock inputs 
Clock up 
Clock down  - 
Count or frequency 
Reset 
Count 
A/B-phase quadrature 
counter 
Phase A 
Phase B 
Count or frequency 
Reset
1
 
Count 
 
1
  For an encoder: Phase Z, Home