Bryan Boilers CLM Dépliant

Pagina di 1
CLM - Atmospheric Series
  
“Compliance+” Ultra Low NOx Water or Steam Boilers 
Air Assisted Gas Fired – Sub 12 PPM
 
 
Form 2367 
 
 Rev 04/21/06     Repl New  
    Page 1 of 1 
 
Please delete these paragraphs from 
the standard CLM Series Boiler Sample 
Specification:(Form 2137 or 2138) 
 
GAS BURNER AND CONTROL EQUIPMENT 
 
The gas burner assembly shall be an integral 
part of the boiler.  Burners shall be tubular alloy 
steel atmospheric type for operation with natural 
draft, requiring no motor or blower.  Gas pilot is 
to be electrically ignited. 
    
The following trim and controls shall be 
furnished: 
1. Pilot 
cock 
2.  Electronic pilot ignition 
3.  Gas pilot safety shutoff valve 
4.  Honeywell Flame Safeguard RM7890A 
5.  Main manual gas shutoff valve 
6.  Electric gas valve operator and auxiliary 
safety shutoff gas valve (CLM120 & 
CLM150) 
7.  Motorized gas valve operator and auxiliary 
safety shutoff gas valve (CLM180 to 
CLM300) 
8.  High gas pressure switch (CLM270 to 
CLM300) 
9.  Pilot and main gas pressure regulators 
   
 
 
And substitute these paragraphs:  
   
Ultra LOW NOX GAS BURNER AND 
CONTROL EQUIPMENT * 
 
The Bryan “Compliance +” boiler shall be 
furnished with a UL listed air assisted Ultra Low 
NOx – Gas burner suitable for operation with 
natural gas.  Burner shall be complete with 
integral motor and blower for supplying sufficient 
combustion air with normal vent conditions. 
 
Burner must be Ultra Low NOx type for reduced 
emissions service.  Burner NOx reduction strategy 
shall reduce the production of NOx by controlling 
low excess air operation and reducing flame 
temperature.  Optimum stoichiometry shall be 
maintained by a fuel metering control with 
adjustments through the modulating range 
assuring NOx reduction and high fuel efficiency. 
 
The special metal fiber burners are provided to 
assure the main flame is combusted properly on 
the burner head. 
 
The natural gas firing, NOx emissions will not 
exceed 12 ppm. 
 
All emissions measurements are to be corrected 
to 3% O
2
 
Control panel (16” x 20”) includes Honeywell 
RMT840L Flame Safe Guard with UV scanner  
 
Supply voltage 240-480/3/60 and includes a 
control circuit air assisted transformer  
 
Natural gas pressure required 20” min/28” max. 
 
The control will have a 5 to 1 turndown.