HP Performance Optimized Data Center (POD) 40cp Guida All'Installazione

Pagina di 21
 
Supported facility connections  18 
Supported facility connections 
Humidifier specifications 
A dedicated supply of domestic water is required if the optional humidifier is installed. For specifications, 
see the humidifier manual supplied with the HP POD. 
 
 
Item 
Component 
Humidifier drain and water supply 
 
For more information about the humidifier, see the documentation developed by the humidifier 
manufacturer. 
 
Convenience outlets 
The HP POD is prewired for a convenience outlet on the inside of the unit. This circuit is not part of the 
power provided by the main switchboard feeding the 3 phase power to the HP POD. To energize this 
circuit, you must supply a dedicated single phase, 16-or 20-amp branch circuit from your facility at the 
appropriate voltage. Make sure that the branch circuit is connected to the prewired exterior mounted 
junction box and that it is wired in accordance with local regulations and codes. 
 
Grounding requirements 
The neutrals and equipment grounding conductors for all 3-phase HP POD feeders must remain isolated. 
The two conductors can be bonded at the power source only. 
Functional and supplementary grounding straps are provided between each rack and HP POD. 
  
 
IMPORTANT:
  Before installing the HP POD, consult your local AHJ for applicable codes and 
to review site-specific location guidelines. If needed, obtain any necessary permits.