HP Performance Optimized Data Center (POD) 40cp Guida All'Installazione

Pagina di 21
 
HP POD specifications  8 
HP POD specifications 
Dimensions 
The HP POD is approximately 12.2 m (40 ft) long, 2.4 m (8 ft) wide, and 2.9 m (9.5 ft) tall. 
 
Weight 
HP POD weight varies, depending on whether the HP POD is empty or configured with IT equipment. 
Computer racks and IT equipment add incremental weight to an empty HP POD and vary, depending on 
customization. 
 
Specification 
Approximate weight 
Empty HP POD 
15,454 kg (34,000 lb) 
Maximum weight of IT 
equipment for each rack 
1,364 kg (3,000 lb) 
Maximum weight of IT 
equipment per HP POD 
30,000 kg (66,000 lb) 
Fully outfitted HP POD 
47,854 kg (105,500 lb) 
 
  
 
IMPORTANT:
  Before moving the HP POD to a new location, HP recommends contacting the 
local Department of Transportation for permit loads and other transportation requirements.  
  
 
External cold aisle view 
 
 
Item 
Component 
1* 
Electrical busway 225A enclosed circuit breaker 
ECS panel 
Auxiliary single phase branch circuit power