4
Installation Guide for Dimming and Switching Panels
Panel Model Number Guide 
(continued)
Prefix
CCP = Custom combination panel
Module Types
_X _L _A _M _F _T
List modules in the order shown above. Insert the
quantity before each module code. Omit codes for
modules not used in panel. See table below for limits
on numbers of modules per panel.
X = Four-Circuit Switching (Relay) (XP)
L = Four-Circuit Dimming (4U)
A = Four-Circuit Adaptive Dimming (4A)
M = Four-Circuit Motor (4M)
F = Four-Circuit Quiet Fan Speed (4FSQ)
T = 0-10 V, DALI (broadcast), DSI, and PWM 
Ballast Control (TVM)
Feed Voltage
120 for 120 V
GRAFIK Systems
TM
(CCP) (120 V
only)
Example
C C P - 2 X 2 L 1 A 4 T - 1 2 0 4 M L - 2 0 - C G P _ _ _
Module Quantity Limits
Panel Size
Feed type
TVM
4A
4U
4M
Mini
Feed-through
NA
Any combination up to 3 modules
Mini
Feed-through
0-4
Any combination up to 2 modules; must have 1 4U or XP module minimum;
each 4U or XP module can control only 2 TVM modules 
Mini
Breakers
NA
Any combination up to 3 modules
Mini
Breakers
0-4
Any combination up to 2 modules; 
must have 1 4U module minimum; 
each 4U module can control only 2 TVM modules
Standard
Feed-through
NA
Any combination up to 9 modules
Standard
Feed-through
0-12
Any combination up to 8 modules; must have 1 4U or XP module minimum;
each 4U or XP module can control only 2 TVM modules
Standard
Breakers (main lugs)
NA
Any combination up to 9 modules
Standard
Breakers (main lugs)
NA
Any combination up to 7 modules
Standard
Breakers (main lugs)
0-12
Any combination up to 8 modules; 
must have 1 4U module minimum; 
each 4U module can control only 2 TVM modules
Standard
Breakers (main lugs)
0-12
Any combination up to 5 modules; must have 1 4U or XP module minimum;
each 4U or XP module can control only 2 TVM modules
Notes
• Consult Lutron for panels with custom breaker needs.
• TVM = 0 is a TVM-ready panel; TVM modules can easily be installed in the future.
• TVM = NA is not TVM-ready
XP
0
0
0
0
Modules: 
Quantity and Type
Prefix
Feed
Voltage
Feed
Type
Custom 
Panel Suffix
(contact Lutron for custom options)
Branch
Circuit
Breaker
Rating
Feed Type / Input Ratings
FT = feed-through panel (circuit breakers not included) / 
120 V
3ML = 1 phase 3 wire feed (split phase) / 120/240 V
4ML = 3 phase 4 wire feed / 120/208 V
2 = 1 phase 2 wire input breakers (mini only)
3 = 1 phase 3 wire input breakers (mini only)
4 = 3 phase 4 wire input breakers (mini only)
Branch Circuit Breaker Rating
20 = 20 A branch circuit breakers
15 = 15 A branch circuit breakers
Custom Panel Suffix (optional)
Indicates panel with special options
Frequency 
(All Model Numbers and Voltages): 50/60 Hz
Output (Load) Ratings
Module Type Rating
XP, 4U
16 A per circuit
4A
16 A per module, 10 A per output
4M
16 A per module, 5 A per output 
(1/4 HP motor)
4FSQ
2 A per output (single ceiling fan)
TVM
50 mA per channel, 750 mA per system