Beck, R&J ELECTRIC ACTUATORS FOR INDUSTRIAL PROCESSCONTROL 11-1_9 Manuale Utente

Pagina di 88
66
COMMUNICATIONS
 
The Beck Digital Control Module (DCM-2) is 
equipped with a serial interface which allows for 
direct communication with a computer.  Using 
a communication cable, connect the DCM-2 to 
the computer using the DCM-2’s RS-232 (J20) 
connector (see illustration on this page) and the 
computer’s COM port.  Ensure that the COM port 
on the computer is active, and that the cable is 
plugged into the proper COM port if more than one 
is present (e.g., COM1, COM2, etc.).  Note that a 
plug end adapter may be necessary for connection 
to the computer’s COM port.  
 
Once connected, communication can be 
established between the DCM-2 and the computer 
using a terminal emulation program, such as 
HyperTerminal
®
.  This method of communication 
will allow for configuration, calibration and 
verification of drive DCM-2 settings without the 
use of custom software applications.
HyperTerminal
®
 Software
 
HyperTerminal is the standard ASCII terminal 
emulation software provided with Microsoft
®
 
 Windows
®
.  If using HyperTerminal
®
, the following 
instructions will assist in setup.  Note that some 
variation to these instructions may be necessary 
depending on the version of HyperTerminal
®
 being 
used.
 
Once the computer has been connected to the 
DCM-2, access HyperTerminal
®
 by clicking first on 
"Start", then "Programs", then "Accessories", then 
"Communications", then "HyperTerminal". 
 
Double-click on the "Hypertrm.exe" icon to start 
the program.  Once HyperTerminal
®
 is running, it is 
necessary to set up a file with the proper settings 
to communicate with the DCM-2.  Proceed as 
follows:
 1.  If prompted to install a modem, answer "no".  
Proceed to enter a name (e.g., "DCM-2") 
and select an icon (any will suffice) in the 
"Connection Description" box.  Click the "OK" 
button.
 2.  The "Connect to" box should open next.  At 
the bottom of the box, set the "Connect using" 
selection to the computer COM port that has 
been connected to the DCM-2.  Click the "OK" 
button.
 3.  The COM port properties box should open next.  
This is where the communication settings are 
established.  The correct settings are:
      a.  Bits per second = "1200"
      b.  Data bits = "8"
     c. Parity = "none"
      d.  Stop bits = "1"
      e.  Flow control = "none"
 4.  With the appropriate settings entered from Step 
3, above, click "OK".  Communications should 
now be enabled.
 5.  Press the "Enter" key twice.  "Ok" should be 
displayed indicating that HyperTerminal
®
 is 
DCM-2 SERIAL INTERFACE
 
Setup
RS-232
CONNECTOR
Hyperterminal
®
 is a product of Hilgraeve, Inc.
POSITION
DEMAND
TRQ/THRUST
STALL
FB OPEN
STOP/LIMIT
ACKNOWLEDGE
TEMP F
CALIBRATE
SET POS
100%
SET DEM
100%
SET DEM
0%
SET POS
0%
R
FWD
REV
STAT
PWR