FlashGuard 2000B Troubleshooting Guide
Page 5
Section 3 Flashhead will not operate in any mode. Control power indicator 
on, high-voltage board LED indicator on.
Possible Cause:
Trigger control board defective, or incorrect DIP switch setting.
Diagnostic Test:
Perform “Flashhead Isolation Test” (pg. 9) and “Power Supply Isolation
Test” (pg.10)  Also compare trigger board DIP switch settings with default
settings in manual.
Corrective Action: Set DIP switches according to specifications. If no trigger output is
observed when performing the flashhead isolation test, replace the trigger
control board.
Possible Cause:
Insufficient trigger voltage to the flashhead.
Diagnostic Test:
If tower height is greater than 340 feet, remove the connector at terminal
E13 on the motherboard, and connect it to E14. This will boost the voltage
to the flashhead by approximately 10%.
Corrective Action: Leave the connector at E14.
Possible Cause
Flashtube and/or trigger transformer faulty.
Diagnostic Test
Perform the Power Supply isolation test to check for trigger pulses.
Corrective Action: If trigger pulses are present and high voltage neon lamp is lit then replace
flashtube and/or trigger transformer.
Section 4 Flashhead operates properly in day mode, but no strobe in night mode
and trips the strobe alarm.
Possible Cause:
Trigger control board faulty.
Diagnostic Test:
Perform “Power Supply Isolation Test” (pg. 11) to check for trigger pulses.
Corrective Action: Replace the trigger control board.
Possible Cause
Diode board DB1 faulty.
Diagnostic Test:
 Remove the two mounting screws on the control panel. Disconnect DB1,
and measure resistance both ways across each diode. Make sure no
diodes have shorts.  If shorted, DB1 is faulty.  Note: The diode board DB1
is located under the control panel where the test switches are.
Corrective Action: Replace DB1.
Section 5 Flashhead operates properly in night mode. No flash in day mode,
strobe alarm is on.
Possible Cause
Trigger control board faulty.
Diagnostic Test
Perform “Power Supply Isolation Test” (pg. 10) to check for trigger pulses.
Corrective Action: Replace the trigger control board if test fails.